Appendix - "Bus analysis" mode
124
12.7.3. Measurements (Ethernet 10Base-T)
Diagnosis
Use this table to troubleshoot problems on a measurement :
Measurement
Description
Diagnosis
VLevel
Measurement of the amplitude on the
signal’s thin pulses
Termination problem
Junction connection (oxidation, bad contact,
etc.)
Cable length not compliant with standard
Significant noise (check the cable route, ground
braid not connected, faulty chassis-ground, etc.)
…
Time Rise
Rise time between 10% and 90% of
the signal amplitude
Unsuitable or damaged cable (the rise and fall
times increase with the cable impedance)
Termination impedance incorrectly positioned
…
Time Fall
Fall time between 90% and 10% of
the signal amplitude
Time Data
Measurement made using the bit time
total. The bit time is measured on one
period (Manchester coding).
The measurement is only made on
thin pulses.
Unsuitable or damaged cable
Significant noise (check the cable route, ground
braid not connected, faulty chassis-ground, etc.)
…
Jitter
Measurement made using the bit time
total
Significant noise (check the cable route, ground
braid not connected, faulty chassis-ground, etc.)
…
Dist
Measurement of the amplitude
distortion.
The max overshoot level is compared
to the signal peak-to-peak value. The
measurement is only made on thick
pulses.
Unsuitable cable impedance
Termination problem (if there is no termination,
major overshoot and the opposite if the bus
impedance is too high)
Significant noise (check the cable route, ground
braid not connected, faulty chassis-ground, etc.)
…