Table of Functions
156
Code
(Comm.
Address)
Name
LCD
Display
Setting Range
Initial Value
Prope
rty*
Ref.
PRT-26
(0h1D1A)
Under load warning
time
UL Warn
Time
0.0
–600.0 (sec)
10.0
O
PRT-27
(0h1D1B)
Under load trip
selection
UL Trip
Sel
0
None
0: None
O
1
Trip&Coast
2
Decel Stop
PRT-28
(0h1D1C)
Under load trip timer
UL Trip
Time
0.0
–600.0 (sec)
30.0
O
PRT-29
(0h1D1D)
Under load trip Retry
Number
UL Retry
Num
0~10
2
O
PRT-30
(0h1D1E)
Under load trip delay
time
UL Retry
Dly
0.0~6000.0 (sec) 10.0
O
PRT-31
(0h1D1F)
Operation on no
motor trip
No Motor
Trip
0
None
0: None
O
1
Trip&Coast
PRT-32
(0h1D20)
No motor trip current
level
No Motor
Level
1
–100 (%)
5
O
PRT-33
(0h1D21)
No motor detection
time
No Motor
Time
0.1
–10.0 (sec)
3.0
O
PRT-34
(0h1D22)
Operation at motor
overheat detection
Thermal-
T Sel
0
None
0: None
O
1
Trip&Coast
2
Decel Stop
PRT-35
(0h1D23)
Thermal sensor input
Thermal
In Src
0
Thermal In
0: Thermal In
O
1
V2
PRT-36
(0h1D24)
Thermal sensor fault
level
Thermal-
T Lev
0.0
–100.0 (%)
50.0
O
PRT-37
(0h1D25)
Thermal sensor fault
range
Thermal-
T Area
0
Low
0: Low
O
1
High
PRT-38
51
(0h1D26)
Motor overheat
detection sensor
Thermal
Monitor
-
-
X
51
PRT-38 is displayed when PRT-
34 is not set to “0 (NONE)”.
Summary of Contents for H100 0008-2(PLUS)
Page 26: ......
Page 30: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 31: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 32: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 33: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 34: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 35: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 46: ...Installing the Inverter 20 200 V 0 75 18 5kW 400 V 0 75 185kW 400 V 220 500kW ...
Page 48: ...Installing the Inverter 22 ...
Page 63: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 207: ...Technical Specification 181 6 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 208: ...Technical Specification 182 110 185 kW 3 phase 220 500 kW 3 phase ...
Page 237: ...211 목차 EN IEC 61800 3 2018 EN 61800 5 1 2007 A1 2017 ...
Page 238: ...212 ...
Page 239: ...213 목차 ...