Table of Functions
129
Code
(Comm.
Address)
Name
LCD Display
Setting Range
Initial
Value
Property* Ref.
of auxiliary motors
is increased
AP1-53
(0h1A35)
Auxiliary motors
start delay time
Stage DT
0.0
–3600.0
(sec)
5.0
O
AP1-54
(0h1A36)
Auxiliary motors
stop delay time
Aux Stop DT
0.0
–3600.0
(sec)
5.0
O
AP1-55
(0h1A37)
Auto change
mode selection
Auto Ch Mode
0 None
1: AUX
Exchange
Δ
1
AUX
Exchange
2
Main
Exchange
AP1-56
(0h1A38)
Alternative interval
setting
Alternate Time
00: 00
–99:
00
72: 00
O
AP1-57
(0h1A39)
Alternate
operating
dondition
frequency
Alternate Level
Low Freq
–
High Freq
20.00
O
AP1-58
(0h1A3A)
Timer display
Auto Op Time
-
0:00
X
AP1-59
(0h1A3B)
Pressure deviation
level for destaging
Destage Pres.
0~60000
500
O
AP1-60
46
(0h1A3C)
Target frequency
of Aux motor
during Multi
Master
Lag Freq
Low Freq ~
High Freq
60.00
O
AP1-61
(0h1A3D)
#1 auxiliary motor
start frequency
Stage Freq 1
Low Freq
–
High Freq
45.00
O
AP1-62
(0h1A3E)
#2 auxiliary motor
start frequency
Stage Freq 2
Low Freq
–
High Freq
45.00
O
AP1-63
(0h1A3F)
#3 auxiliary motor
start frequency
Stage Freq 3
Low Freq
–
High Freq
45.00
O
AP1-64
(0h1A40)
#4 auxiliary motor
start frequency
Stage Freq 4
Low Freq
–
High Freq
45.00
O
46
API-60 only appears when AP1-
40 MMC Sel is set to “2” or “3”.
Summary of Contents for H100 0008-2(PLUS)
Page 26: ......
Page 30: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 31: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 32: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 33: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 34: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 35: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 46: ...Installing the Inverter 20 200 V 0 75 18 5kW 400 V 0 75 185kW 400 V 220 500kW ...
Page 48: ...Installing the Inverter 22 ...
Page 63: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 207: ...Technical Specification 181 6 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 208: ...Technical Specification 182 110 185 kW 3 phase 220 500 kW 3 phase ...
Page 237: ...211 목차 EN IEC 61800 3 2018 EN 61800 5 1 2007 A1 2017 ...
Page 238: ...212 ...
Page 239: ...213 목차 ...