Quick Start Reference
Q
x
Codes / Functions
Description
DRV-01
Cmd Frequency
Frequency reference in AUTO mode when DRV-07
is set to’ KeyPad’.
DRV-02
KeyPad Run Dir
Rotation direction of the keypad command in the HAND or AUTO mode.
Settings
Description
0
Forward
Fx operation
1
Reverse
Rx operation
DRV-05
KPD H.O.A Lock
To make HAND-OFF-AUTO enabled/disabled
Settings
Description
0
Locked
To make HAND-OFF-AUTO disabled and turn Auto mode
1
During
Run
If [DRV-06 cmd source] is Fx/Rx-1, Fx/Rx-2, int485 or
fieldbus, Hand-off-auto is enabled only when Off
2
OFF Key
Enable
Under the same conditions as During Run, only the OFF
key is activated. (Factory Default)
3
Unlocked
To make HAND-OFF-AUTO enabled
DRV-08 AUTO
Mode Sel
Set whether to use AUTO mode.
0. Enabled
1. Disabled (Factory default)
DRV-24 Hand Key
Sel
This function enables/disables the HAND key on the keypad.
Settings
Description
0
None
Follow the settings of [DRV-05 KPD H.O.A Lock].
1
Disabled
Regardless of the setting of [DRV-05 KPD H.O.A Lock], the
HAND key is disabled.
DRV-25
HAND Cmd Freq
Frequency displayed at the monitor display item (Monitor Line-1) when the HAND
key is pressed in other modes (default frequency reference for HAND mode).
DRV-26
Hand Ref Mode
Set Hand frequency reference source
(Typically Drive Keypad)
.
0. Hand Parameter
1. V1
2. V2
3. V3
4. I2
5. I3
6. Follow Auto
OUT-31
–36
Relay 1
–5
Set AUTO State (36) to ensure that the inverter is in AUTO mode.
OUT-31
–36
Relay 1
–5
Set HAND State (37) to ensure that the inverter is in HAND mode.
Summary of Contents for H100 0008-2(PLUS)
Page 26: ......
Page 30: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 31: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 32: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 33: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 34: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 35: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 46: ...Installing the Inverter 20 200 V 0 75 18 5kW 400 V 0 75 185kW 400 V 220 500kW ...
Page 48: ...Installing the Inverter 22 ...
Page 63: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 207: ...Technical Specification 181 6 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 208: ...Technical Specification 182 110 185 kW 3 phase 220 500 kW 3 phase ...
Page 237: ...211 목차 EN IEC 61800 3 2018 EN 61800 5 1 2007 A1 2017 ...
Page 238: ...212 ...
Page 239: ...213 목차 ...