Troubleshooting
171
LCD Display
Description
the detection level at PRT-66.
Fire Mode
When there is a fire, Fire Mode forces the inverter to ignore certain fault
trips and continue to operate. Set the digital output terminals or relay
(OUT-31
–35 or OUT-36) to ‘27 (Fire Mode)’ to receive the fire mode
warning output signals.
Pipe Broken
Displayed when a pipe is broken during pump operation. Set the digital
output terminals or relay (OUT-31
–35 or OUT-36) to ‘28 (Pipe Broken)’ to
receive the pipe break warning output signals.
Lost Keypad
Displayed when a communication error occurs between the keypad and
the inverter, when PRT-11 (Lost KPD Mode) is set to any other value
than ‘0’, and a run command is given from the keypad. Set the digital
output terminals or relay (OUT-31
–35 or OUT-36) to ‘24 (Lost KPD)’ to
receive the lost keypad warning output signals.
Level Detect
Displayed during a level detect state. Set PRT-
70 to ‘1 (warning)’ to enable.
CAP. Warning
Displayed when capacitor life expectancy level goes below the level set by
the user. Set the digital output terminals or relay (OUT-31
–35 or OUT-36)
to ‘34 (CAPWarning)’ to receive the capacitor life warning output signals.
Fan ExChange
Displayed when the cooling fans need replacing. Set the digital output
terminals or relay (OUT-31
–35 or OUT-36) to ‘35 (FanExChange)’ to
receive the fan replacement warning output signals.
Low Battery
Displayed when the RTC battery voltage drops to or below 2 V. To
receive a warning output signal, set PRT-90 (Low Battery) to
‘Yes’.
Broken Belt
Displayed when PRT-91 is set to warning and the inverter becomes on
the condition of broken belt.
Load Tune
Displayed when the values of
‘AP2-03 and AP2-04’ are more than the
values of
‘AP2-09 and AP2-10’ and the function of load tuning is not normal.
PareWrite Fail
Displayed when the function of smart copier is not normal.
Rs Tune Err
Displayed when the function of Rs tuning is not normal . For example,
auto tuning is performed without wiring the motor.
Lsig Tune Err
Displayed when the function of Lsigma tuning is not normal . For
example, auto tuning is performed without wiring the motor.
KPD H.O.A Lock
If [DRV-05 KPD H.O.A Lock] sets HAND-OFF-AUTO disabled, it lasts
one second when HAND-OFF-AUTO key is pressed using user keypad
InFan Warning
It occurs when an abnormality is detected in the cooling fan inside the
inverter with inverter capacity of 110 kW to 500 kW.
Sleep
Indicates that PID operation standby (Sleep) mode is in place.
Summary of Contents for H100 0008-2(PLUS)
Page 26: ......
Page 30: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 31: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 32: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 33: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 34: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 35: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 46: ...Installing the Inverter 20 200 V 0 75 18 5kW 400 V 0 75 185kW 400 V 220 500kW ...
Page 48: ...Installing the Inverter 22 ...
Page 63: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 207: ...Technical Specification 181 6 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 208: ...Technical Specification 182 110 185 kW 3 phase 220 500 kW 3 phase ...
Page 237: ...211 목차 EN IEC 61800 3 2018 EN 61800 5 1 2007 A1 2017 ...
Page 238: ...212 ...
Page 239: ...213 목차 ...