Troubleshooting
167
LCD Display
Type
Description
rated current.
Over Voltage
Latch
Displayed when internal DC circuit voltage exceeds the
specified value.
Low Voltage
Level
Displayed when internal DC circuit voltage is less than the
specified value.
Low Voltage2
Latch
Displayed when internal DC circuit voltage is less than the
specified value during inverter operation.
Ground Trip
Latch
Displayed when a ground fault trip occurs on the output side of
the inverter and causes the current to exceed the specified
value. The specified value varies depending on inverter
capacity.
E-Thermal
Latch
Displayed based on inverse time-limit thermal characteristics to
prevent motor overheating. Operates when PRT-40 is set to a
value other than ‘0’.
Out Phase Open Latch
Displayed when a 3-phase inverter output has one or more
phases in an open circuit condition. Operates when bit 1 of
PRT-
05 is set to ‘1’.
In Phase Open
Latch
Displayed when a 3-phase inverter input has one or more
phases in an open circuit condition. Operates only when bit 2
of PRT-
05 is set to ‘1’.
Inverter OLT
Latch
Displayed when the inverter has been protected from overload
and resultant overheating, based on inverse time-limit thermal
characteristics. Allowable overload rates for the inverter are
120% for 1 min and 140% for 5 sec.
No Motor Trip
Latch
Displayed when the motor is not connected during inverter
operation. Operates when PRT-
31 is set to ‘1’.
Protection Functions Using Abnormal Internal Circuit Conditions and External
Signals
LCD Display
Type
Description
Over Heat
Latch
Displayed when the temperature of the inverter heat sink
exceeds the specified value.
Over Current2
Latch
Displayed when the DC circuit in the inverter detects a
specified level of excessive, short circuit current.
External Trip
Latch
Displayed when an external fault signal is provided by the
multi-function terminal. Set one of the multi-function input
terminals at IN-65-
71 to ‘4 (External Trip)’ to enable external
Summary of Contents for H100 0008-2(PLUS)
Page 26: ......
Page 30: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 31: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 32: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 33: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 34: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 35: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 46: ...Installing the Inverter 20 200 V 0 75 18 5kW 400 V 0 75 185kW 400 V 220 500kW ...
Page 48: ...Installing the Inverter 22 ...
Page 63: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 207: ...Technical Specification 181 6 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 208: ...Technical Specification 182 110 185 kW 3 phase 220 500 kW 3 phase ...
Page 237: ...211 목차 EN IEC 61800 3 2018 EN 61800 5 1 2007 A1 2017 ...
Page 238: ...212 ...
Page 239: ...213 목차 ...