Installing the Inverter
48
Remarque
Si la commande avant (Fx) est activée, le moteur doit tourner dans le sens anti-horaire si
on le regarde côté charge du moteur. Si le moteur tourne dans le sens inverse, inverser
les câbles aux bornes U et V.
Verifying the Motor Rotation
1
On the keypad, set DRV-
07 to ‘1 (Keypad)’.
2
Set a frequency reference.
3
If the inverter is in OFF mode, press the [AUTO] key twice on the keypad to operate
the inverter in the forward (Fx) direction.
4
If the inver ter is operating in AUTO mode, press the [AUTO] key once on the keypad
to operate the inverter in the forward (Fx) direction.
5
Observe the motor’s rotation from the load side and ensure that the motor rotates
counterclockwise (forward).
•
Check the parameter settings before running the inverter. Parameter settings may have to
be adjusted depending on the load.
•
To avoid damaging the inverter, do not supply the inverter with an input voltage that
exceeds the rated voltage for the equipment.
•
Before running the motor at m
aximum speed, confirm the motor’s rated capacity. As
inverters can be used to easily increase motor speed, use caution to ensure that motor
speeds do not accidently exceed the motor’s rated capacity.
Summary of Contents for H100 0008-2(PLUS)
Page 26: ......
Page 30: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 31: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 32: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 33: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 34: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 35: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 46: ...Installing the Inverter 20 200 V 0 75 18 5kW 400 V 0 75 185kW 400 V 220 500kW ...
Page 48: ...Installing the Inverter 22 ...
Page 63: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 207: ...Technical Specification 181 6 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 208: ...Technical Specification 182 110 185 kW 3 phase 220 500 kW 3 phase ...
Page 237: ...211 목차 EN IEC 61800 3 2018 EN 61800 5 1 2007 A1 2017 ...
Page 238: ...212 ...
Page 239: ...213 목차 ...