Troubleshooting
168
LCD Display
Type
Description
trip.
BX
Level
Displayed when the inverter output is blocked by a signal
provided from the multi-function terminal. Set one of the multi-
function input terminals at IN-65-
71 to ‘5 (BX)’ to enable input
block function.
H/W-Diag
Fatal
Displayed when an error is detected in the memory
(EEPRom), analog-digital converter output (ADC Off Set) or
CPU watchdog (Watch Dog-1, Watch Dog-2).
EEP Err: An error in reading/writing parameters due to keypad
or memory (EEPRom) fault.
ADC Off Set: An error in the current sensing circuit
(U/V/W terminal, current sensor, etc.).
NTC Open
Latch
Displayed when an error is detected in the temperature sensor
of the Insulated Gate Bipolar Transistor (IGBT).
Fan Trip
Latch
Displayed when an error is detected in the cooling fan. Set
PRT-
79 to ‘0’ to activate fan trip (for models below 22 kW
capacity).
InFan Trip
Latch
It occurs when an abnormality is detected in the cooling fan
inside the inverter with inverter capacity of 110 kW to 500 kW.
Selecting PRT - 79 code to 0 will work.
Thermal Trip
Latch
Triggered when the input temperature is higher than the
temperature set by the user.
Lost KeyPad
Latch
Triggered when a communication error occurs between the
keypad and the inverter, when the keypad is the command
source, and PRT-11 (Lost KPD Mode) is set to any other value
than ‘0’.
Fuse Open
Latch
If an input stage fuse breaks with an inverter of 315 kW or
more, a fault will occur.
Summary of Contents for H100 0008-2(PLUS)
Page 26: ......
Page 30: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 31: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 32: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 33: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 34: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 35: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 46: ...Installing the Inverter 20 200 V 0 75 18 5kW 400 V 0 75 185kW 400 V 220 500kW ...
Page 48: ...Installing the Inverter 22 ...
Page 63: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 207: ...Technical Specification 181 6 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 208: ...Technical Specification 182 110 185 kW 3 phase 220 500 kW 3 phase ...
Page 237: ...211 목차 EN IEC 61800 3 2018 EN 61800 5 1 2007 A1 2017 ...
Page 238: ...212 ...
Page 239: ...213 목차 ...