Technical Specification
176
Three Phase 400 V (30.0
–90.0 kW)
Model
H100 XXXX–4 (PLUS)
0300
0370
0450
0550
0750
0900
Applied
Motor
Heavy Duty
HP
30
40
50
60
75
100
kW
22
30
37
45
55
75
Normal Duty
HP
40
50
60
75
100
125
kW
30
37
45
55
75
90
Rated
output
Rated Capacity (kVA)
46.5
57.1
69.4
82.0
108.2
128.8
Rated
Current
(A)
Three-
Phase
HD
41
55
67
81
106
136
ND
61
75
91
107
142
169
Single-Phase
36
39
47
55
73
86
Output Frequency
0
–400 Hz
Output Voltage (V)
3-Phase 380
–480 V
Rated
input
Working
Voltage (V)
Three-Phase 3-Phase 380
–480 VAC (-15%–+10%)
Single-
Phase
1-Phase 480 VAC (-5%
–+10%)
Input
Frequency
Three-Phase 50
–60 Hz (
5%)
Single-
Phase
50
–60 Hz (
5%)
Rated Current (A)
69.1
69.3
84.6
100.1
133.6
160.0
Weight (kg)
7.5
26
35
35
43
43
•
The standard motor capacity is based on a standard 4-pole motor.
•
The standard used for 200 V inverters is based on a 220 V supply voltage, and 400 V
inverters are based on a 440 V supply voltage.
•
The rated output current is limited based on the carrier frequency set at CON-04.
Summary of Contents for H100 0008-2(PLUS)
Page 26: ......
Page 30: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 31: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 32: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 33: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 34: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 35: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 46: ...Installing the Inverter 20 200 V 0 75 18 5kW 400 V 0 75 185kW 400 V 220 500kW ...
Page 48: ...Installing the Inverter 22 ...
Page 63: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 207: ...Technical Specification 181 6 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 208: ...Technical Specification 182 110 185 kW 3 phase 220 500 kW 3 phase ...
Page 237: ...211 목차 EN IEC 61800 3 2018 EN 61800 5 1 2007 A1 2017 ...
Page 238: ...212 ...
Page 239: ...213 목차 ...