Troubleshooting
170
Option Protection
LCD Display
Type
Description
Lost Command
Level
Displayed when a frequency or operation command error is
detected during inverter operation by controllers other than the
keypad (e.g., using a terminal block and a communication
mode). Activate by setting PRT-
12 to any value other than ‘0’.
IO Board Trip
Latch
Displayed when the I/O board or external communication card
is not connected to the inverter or there is a bad connection.
TB Trip
Latch
It occurs when the control terminal block (Terminal Bolck) is
disconnected or the contact state is bad.
ParaWrite Trip
Latch
Displayed when communication fails during parameter writing.
Occurs due to a control cable fault or a bad connection.
Option Trip-1
Latch
Displayed when a communication error is detected between
the inverter and the communication board. Occurs when the
communication option card is installed.
5.1.2 Warning Message
LCD Display
Description
Over Load
Displayed when a motor is overloaded. Set PRT-
17 to ‘1’ to enable. Set
OUT-31
–35 or OUT-36 to ‘5 (Over Load)’ to receive the overload warning
output signals.
Under Load
Displayed when the motor is underloaded. Set PRT-
25 is to ‘1’. Set the
digital output terminal or relay (OUT-31
–35 or OUT-36) to’ 7 (Under
Load)’ to receive the underload warning output signals.
INV Over Load
Displayed when the overload time equivalent to 60% of the inverter
overheat protection (inverter IOLT) level, is accumulated. Set the digital
output terminals or relay (OUT-31
–35 or OUT-36) to ‘6 (IOL)’ to receive
the inverter overload warning output signals.
Lost Command
Lost command warning alarm occurs even with PRT-
12 set to ‘0’. The
warning alarm occurs based on the condition set at PRT-13-15. Set the
digital output terminals or relay (OUT-31
–35 or OUT-36) to ‘13 (Lost
Command
)’ to receive the lost command warning output signals.
Fan Warning
Displayed when an error is detected from the cooling fan while PRT-79 is
set to’1’. Set the digital output terminals or relay (OUT-31–35 or OUT-36)
to ‘8 (Fan Warning)’ to receive the fan warning output signals.
DB Warn %ED
Displayed when the DB resistor usage rate exceeds the set value. Set
Summary of Contents for H100 0008-2(PLUS)
Page 26: ......
Page 30: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 31: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 32: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 33: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 34: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 35: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 46: ...Installing the Inverter 20 200 V 0 75 18 5kW 400 V 0 75 185kW 400 V 220 500kW ...
Page 48: ...Installing the Inverter 22 ...
Page 63: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 207: ...Technical Specification 181 6 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 208: ...Technical Specification 182 110 185 kW 3 phase 220 500 kW 3 phase ...
Page 237: ...211 목차 EN IEC 61800 3 2018 EN 61800 5 1 2007 A1 2017 ...
Page 238: ...212 ...
Page 239: ...213 목차 ...