Technical Specification
177
Three Phase 400 V (110.0
–500.0 kW)
Model
H100 XXXX–4 (PLUS) 1100 1320 1600 1850 2200 2500 3150 3550 4000 5000
Applied
Motor
Heavy
Duty
HP
125
150
200
250
250
300
400
450
500
650
kW
90
110
132
160
185
220
250
315
355
400
Normal
Duty
HP
150
200
250
300
350
400
500
550
650
800
kW
110
132
160
185
220
250
315
355
400
500
Rated
output
Rated Capacity
(kVA)
170
201
248
282
329
367
467
520
587
733
Rated
Current
(A)
HD
169
195
255
303
345
375
478
541
591
740
ND
223
264
325
370
432
481
613
683
770
962
Output Frequency 0
–400 Hz
Output Voltage (V) 3-Phase 380
–500 V
Rated
input
Working
Voltage
(V)
Three
Phase
3-Phase 380
–500VAC (-15%–+10%)
Input
Frequenc
y
Three
Phase
50
–60 Hz (
5%)
Rated Current (A)
215.1 254.6 315.3 358.9 419.1 469.3 598.1 666.4 751.3 938.6
Weight (kg)
55.8
55.8
74.7
74.7 120.0 120.0 185.5 185.5 185.5
265
•
The standard motor capacity is based on a standard 4-pole motor and is based on
3-phase
•
The standard used for 200 V inverters is based on a 220 V supply voltage, and 400 V
inverters are based on a 440 V supply voltage.
•
The rated output current is limited based on the carrier frequency set at CON-04.
Summary of Contents for H100 0008-2(PLUS)
Page 26: ......
Page 30: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 31: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 32: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 33: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 34: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 35: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 46: ...Installing the Inverter 20 200 V 0 75 18 5kW 400 V 0 75 185kW 400 V 220 500kW ...
Page 48: ...Installing the Inverter 22 ...
Page 63: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 207: ...Technical Specification 181 6 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 208: ...Technical Specification 182 110 185 kW 3 phase 220 500 kW 3 phase ...
Page 237: ...211 목차 EN IEC 61800 3 2018 EN 61800 5 1 2007 A1 2017 ...
Page 238: ...212 ...
Page 239: ...213 목차 ...