Technical Specification
202
Note
•
It is not necessary to use option type dynamic braking unit for H100+
0.75~18.5kW(200V) and 0.75~30kW(400V) because basically the dynamic braking unit
is built in.
•
The resistance/rated capacity/braking torque/%ED of DB Resistor are valid only for the
DB unit of type A and the values of DB Resistor for type B and C refer to the manual of
DB Unit..
•
Rating Watt of DBU has to be doubled when %ED is doubled.
6.8 Inverter Continuous Rated Current Derating
Derating by carrier frequency
The continuous rated current of the inverter is limited based on the carrier frequency. Refer
to the following graph.
<200[V], 0.75[kW]
–18.5[kW], 400[V] 0.75–30[kW] Current Derating Rate>
Summary of Contents for H100 0008-2(PLUS)
Page 26: ......
Page 30: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 31: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 32: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 33: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 34: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 35: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 46: ...Installing the Inverter 20 200 V 0 75 18 5kW 400 V 0 75 185kW 400 V 220 500kW ...
Page 48: ...Installing the Inverter 22 ...
Page 63: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 207: ...Technical Specification 181 6 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 208: ...Technical Specification 182 110 185 kW 3 phase 220 500 kW 3 phase ...
Page 237: ...211 목차 EN IEC 61800 3 2018 EN 61800 5 1 2007 A1 2017 ...
Page 238: ...212 ...
Page 239: ...213 목차 ...