Electrical connection
88
BCL 548
i
Leuze electronic
7.3.1
PROFINET-IO wiring
A Cat. 5 Ethernet cable should be used for wiring.
For the connection technology transition from M12 to RJ45, a "KDS ET M12 /
RJ 45 W - 4P" adapter is available that lets you connect standard network cables.
If no standard network cables are to be used (e.g. due to lacking IP… protection class), you
can use the "KB ET - … - SA" user-configurable cable on the BCL 548
i
connection cable for the BCL 548i" on page 232.
The individual BCL 548
i
devices in a linear topology are connected with the "KB ET - … -
SSA" cable, see table 13.8 "Bus connection cable for the BCL 548i" on page 232.
For unavailable cable lengths, you can configure your cables yourself. When doing so, make
certain that you connect
TD+
on the M12 connector with
RD+
on the RJ-45 connector and
TD-
on the M12 connector with
RD-
on the RJ-45 connector, respectively, etc.
Notice!
Use the recommended connectors / sockets or the ready-made cables (see chapter 13
"Type overview and accessories").
7.4
Cable lengths and shielding
Observe the following maximum cable lengths and shielding types:
Connection
Interface
Max. cable length
Shielding
BCL – service
USB
3m
shielding absolutely
necessary acc. to USB
specifications
BCL – host
PROFINET-IO RT
100m
absolutely required, shielded
Network from the
first BCL to the last
BCL
PROFINET-IO RT
the maximum segment length
must not exceed 100m for
100Base-TX Twisted Pair
(min. Cat. 5)
absolutely required, shielded
BCL – power supply
unit
30m
not necessary
Switching input
10m
not necessary
Switching output
10m
not necessary
Table 7.4:
Cable lengths and shielding