Diagnostics and troubleshooting
Leuze electronic
BCL 548
i
225
TNT
35/7-2
4
V
12.1
General causes of errors
12.2
Interface errors
Error
Possible error cause
Measures
Status LED
PWR
Off
• No supply voltage connected to the device
• Hardware error
• Check supply voltage
• Send device to customer service
Red, flashing
• Warning
• Query diagnostic data and carry out the resulting
measures
Red, continuous light
• Error: no function possible
• Internal device error, send in device
Orange, continuous light
• Device in service mode
• Reset service mode with webConfig tool or
display
Status LED
BUS
Off
• No supply voltage connected to the device
• Device not yet recognized by the PROFINET-IO
• Hardware error
• Check supply voltage
• Send device to customer service
• Send device to customer service
Red, flashing
• Communication error: Parameterization or config-
uration failed, IO error: No data exchange
• Check interface
• Can be corrected by resetting
Red, continuous light
• Communication error on the PROFINET-IO: No
communication to IO Controller established ("no
data exchange")
• Check interface
• Cannot be corrected by resetting
• Send device to customer service
Table 12.1:
General causes of errors
Error
Possible error cause
Measures
No communication via USB
service interface
• Incorrect connection cable
• Connected BCL 548
i
is not detected
• Check connection cable
• Install USB driver
No communication via
PROFINET-IO
BUS
status LED continuous
red light
• Incorrect wiring
• Different protocol settings
• Protocol not released
• Wrong termination
• Incorrect device name set
• Incorrect configuration
• Check wiring
• Check protocol settings
• Activate TCP/ IP or UDP
• Check termination
• Check device name
• Check configuration of the device in the configuration tool
Sporadic errors at the
PROFINET-IO
• Incorrect wiring
• Effects due to EMC
• Overall network expansion exceeded
• Check wiring
• In particular, check wire shielding
• Check the cable used
• Check shielding (shield covering in place up to the clamp-
ing point)
• Check grounding concept and connection to functional
earth (FE)
• Avoid EMC coupling caused by power cables laid parallel
to device lines
• Check max. network expansion as a function of the max.
cable lengths
Table 12.1:
Interface error