Commissioning and configuration
Leuze electronic
BCL 548
i
147
TNT
35/7-2
4
V
10.8.5
Module 14 – Interlinked read result
PROFINET-IO module identifier
Module-ID 1014
Submodule-ID 1
Description
This module is used to switch to a mode in which all decoding results within one reading
gate are combined into a single read result.
Parameter
Parameter length
1 byte
Input data
None
Output data
None
Notice!
An interlinked read result also requires Module 12 – Multi-label. In this mode, the additional
information transmitted in modules 31ff relates to the last decoding result in the chain.
Parameter
Description
Addr.
Data type
Value range
Default
Unit
Delimiter
This parameter is used to define a delim-
iter that is inserted between two individ-
ual decoding results.
0
UNSIGNED8
1 … 255
0:No delimiter is
used.
’;’
-
Table 10.14:
Parameters for module 13