Online commands
218
BCL 548
i
Leuze electronic
Requesting parameter data set from BCL 548
i
Command
’PR’
Description
The parameters of the BCL 548
i
are grouped together in a parameter set and perma-
nently stored in memory. There is one parameter set in permanent memory and one
operating parameter set in volatile memory; in addition, there is a default parameter
set (factory parameter set) for initialization. This command can be used to edit the first
two parameter sets (in permanent and volatile memory). A check sum can be used for
reliable parameter transfer.
Parameter
’PR<BCC type><PS type><Address><Data length>[<BCC>]’
<BCC type>
Check-digit function during transfer,
unit [dimensionless]
’0’
Not used
’3’
BCC mode 3
<PS type>
Memory from which the values are to be read,
unit [dimensionless]
’0’
Parameter values stored in the flash memory
’1’
Reserved
’2’
Default values
’3’
Operating values in RAM
<Address>
Relative address of the data within the data set
’aaaa’
Four-digit, unit [dimensionless]
<Data length>
Length of the parameter data to be transferred
’bbbb’
Four-digit, unit [length in bytes]
<BCC>
Check sum calculated as specified under BCC type