Commissioning and configuration
Leuze electronic
BCL 548
i
129
TNT
35/7-2
4
V
10.5
Commissioning via the PROFINET-IO
10.5.1
General information
The BCL 548
i
is designed as a modular field device. As is the case for PROFIBUS devices,
the PROFINET-IO functionality of the device is defined via parameter sets that are combined
in modules (slots) and sub-modules (sub-slots). The further addressing within subslots is
then accomplished via an index. The modules are included in a XML-based GSD file, which
is supplied as an integral part of the device. By using a user-specific configuration tool, such
as, e.g., Simatic Manager for the programmable logic control by Siemens, the required
modules are integrated into a project during commissioning and its settings and parameters
are adjusted accordingly. These modules are provided by the GSD file.
Notice!
All input and output modules described in this documentation are described from the con-
troller's perspective (IO Controller):
- Input data arrives at the controller.
- Output data is sent out by the controller.
Detailed information on how to prepare the control and the GSD file may be found in chapter
"Configuration steps for a Siemens Simatic S7 control" on page 118.
For the default settings of the
BCL 548
i
, please refer to the following module descriptions.
Notice!
Please note that the set data is overwritten by the PLC!
Some controls make available a so-called "universal module". This module must not be acti-
vated for the
BCL 548
i
!
From the perspective of the device, a distinction is made between PROFINET-IO parameters
and internal parameters. PROFINET-IO parameters are all parameters that can be changed
via the PROFINET-IO and are described in the following modules. Internal parameters, on
the other hand, can only be changed via a service interface and retain their value even
following a PROFINET-IO configuration.
During the configuration phase, the BCL receives parameter telegrams from the
IO Controller (master). Before this is evaluated and the respective parameter values are set,
all PROFINET-IO parameters are reset to default values. This ensures that the parameters
of modules that are not selected are set to the default values.