Watch the procedure
A video of this procedure is available at
https://www.youtube.com/playlist?list=PLYV5R7hVcs-
Figure 59. Simple-swap drive installation
Step 1. Ensure that the drive handle is in the open position. Slide the drive into the drive bay until it snaps
into position.
Step 2. Rotate the tray handle to the closed position.
Complete the parts replacement. See “Complete the parts replacement” on page 164.
Backplane replacement
Use this information to remove and install the backplane.
Remove the 3.5-inch-drive backplane
Use this information to remove the 3.5-inch-drive backplane.
Ground package before opening”
Before removing the backplane:
1. Remove the top cover. See “Remove the top cover” on page 56.
2. Remove all the installed drives and drive fillers (if any) from the drive bays. See “Remove a hot-swap
To remove the backplane, complete the following steps:
Watch the procedure
82
ThinkSystem SR550 Maintenance Manual