background image

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-2457  P. 1 / 2

INSTRUCTION MANUAL

CURRENT LOOP SUPPLY

(applicable to HART signal, opencircuit detection selectable)

MODEL

M5DYH2

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Signal conditioner ...............................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES OR UK LEGISLATION

• The equipment must be mounted inside a panel.

• Insert a noise filter for the power source, input and out-

put connected to the unit.  COSEL Noise Filter Model 

NAC-06-472, TDK Noise Filter Model ZCAT 3035-1330 or 

equivalent is recommended.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may affect 

the protection level of this unit when it is integrated in 

a panel system.  The user may have to review the CE or 

UKCA requirements in regard to the whole system and 

employ additional protective measures* to ensure the CE 

or UKCA conformity.

* For example, installation of noise filters and clamp fil-

ters for the power source, input and output connected 

to the unit, etc.

 

POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and 

confirm its operational range as indicated below:

    24V DC rating: 24V ±10%, approx. 2W

 

GENERAL PRECAUTIONS

• Before you remove the unit or mount it, turn off the power 

supply and input signal for safety.

 

ENVIRONMENT

• Indoor use.

• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 

ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -5 to +55°C     

(23 to 131°F) with relative humidity within 0 to 90% RH 

in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

• Install lightning surge protectors for those wires connect-

ed to remote locations.  For 24V DC power supply line, 
choose a surge protector with its maximum surge voltage 
40V or less between lines.  Recommended M-System mod-
el: MDP-D24.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

COMPONENT IDENTIFICATION

Power LED

Terminal Cover

Zero Adj.

Span Adj.

Body

Specifications

INSTALLATION

Set the unit so that its DIN rail adapter is at the bottom.

 

MOUNTING THE UNIT ON A DIN RAIL

A) Hang the upper hook at the rear side of unit on the DIN 

rail.

B) Push in the lower in keeping pressing the unit to the DIN 

rail.

A

B

DIN Rail

 

REMOVING THE UNIT

A) Push down the DIN rail adaptor using a minus screw-

driver.

B) Pull out the lower part of the unit.
C) Remove the upper part from the DIN rail.

A

C

B

Spring Loaded

DIN Rail Adaptor

Reviews: