This message is for the use case when an implementation has detected a Sensor transitioned to critical
from less severe.
Severity: Error
Serviceable: Yes
Automatically notify Support: No
Alert Category: Critical - Power
SNMP Trap ID: 4
CIM Prefix: PLAT CIM ID: 0522
User Action:
Complete the following steps:
1. Ensure that power supply units are supported and meet the system specifications in wattage and
efficiency level.
2. Check the event log in System Management Module 2 (SMM2) for more detailed information.
3. If the problem still exists, please contact Lenovo support.
•
FQXSPPW0063M: Sensor [SensorElementName] has transitioned to critical from a less severe
state.
This message is for the use case when an implementation has detected a Sensor transitioned to critical
from less severe.
Severity: Error
Serviceable: Yes
Automatically notify Support: No
Alert Category: Critical - Voltage
SNMP Trap ID: 1
CIM Prefix: PLAT CIM ID: 0522
User Action:
Complete the following steps:
1. Reseat the faulty node in the DA240 Enclosure (AC cycle).
2. Check if multiple compute nodes in the DA240 Enclosure are reporting SysBrd Vol fault:
3. If the fault is reported by one single node, replace the failing node with a good one.
4. If fault follows the node, please replace the defective node tray (trained technician only).
5. If the fault follows the slot within the DA240 Enclosure, please replace the shuttle (trained technician
only).
6. If there is a multiple-node failure in an enclosure, AC cycle the entire enclosure by disconnecting the
power cords and plugging them back into system again.
7. If the problem persists, repeat Step 2.
•
FQXSPPW2001I: [PowerSupplyElementName] has been removed from container
[PhysicalPackageElementName].
This message is for the use case when an implementation has detected a Power Supply has been
removed.
Severity: Info
Serviceable: No
Automatically notify Support: No
Alert Category: System - Other
SNMP Trap ID: 22
CIM Prefix: PLAT CIM ID: 0085
.
133