02010008: SMM2 Brd 1.15V: Voltage sensor, warning event was asserted, reading value %V
(Threshold %V)
Asserted when voltage sensed on 1.15V power rail is lower than lower non-critical threshold.
Severity: Warning
Alert Category: System - SMM2 system event
SNMP Trap ID: 33619976
User Action:
1. Virtual reset SMM2 via Web GUI or IPMI command.
2. If the event persists, ensure all populated compute nodes are completely power off, then reseat
SMM2 module. (Service technician only)
3. If the event persists, ensure all populated compute nodes are completely power off, then replace the
SMM2 module. (Service technician only)
4. If the event persists, please consult with technical service.
•
02010009: SMM2 Brd 1.2V: Voltage sensor, warning event was asserted, reading value %V
(Threshold %V)
Asserted when voltage sensed on 1.2V power rail is lower than lower non-critical threshold.
Severity: Warning
Alert Category: System - SMM2 system event
SNMP Trap ID: 33619977
User Action:
1. Virtual reset SMM2 via Web GUI or IPMI command.
2. If the event persists, ensure all populated compute nodes are completely power off, then reseat
SMM2 module. (Service technician only)
3. If the event persists, ensure all populated compute nodes are completely power off, then replace the
SMM2 module. (Service technician only)
4. If the event persists, please consult with technical service.
•
0201000A: SMM2 Brd 2.5V: Voltage sensor, warning event was asserted, reading value %V
(Threshold %V)
Asserted when voltage sensed on 2.5V power rail is lower than lower non-critical threshold.
Severity: Warning
Alert Category: System - SMM2 system event
SNMP Trap ID: 33619978
User Action:
1. Virtual reset SMM2 via Web GUI or IPMI command.
2. If the event persists, ensure all populated compute nodes are completely power off, then reseat
SMM2 module. (Service technician only)
3. If the event persists, ensure all populated compute nodes are completely power off, then replace the
SMM2 module. (Service technician only)
4. If the event persists, please consult with technical service.
•
0201000B: SMM2 Brd 3.3V: Voltage sensor, warning event was asserted, reading value %V
(Threshold %V)
Asserted when voltage sensed on 3.3V power rail is lower than lower non-critical threshold.
Severity: Warning
Alert Category: System - SMM2 system event
.