PS200 Configuration & Operation Guide
OPTIONS & FEATURES
Page 74
Parameter
Name
Value/Range
NOTES
23.01
VIBRATION ALARM
NOT SEL
[default]
ALARM
FAULT
Selecting ALARM will configure
PumpSmart to issue a Keypad or DCS
notice and will trigger a Relay Output
(if configured).
If FAULT is selected, the drive will also
stop the pump.
23.02
VIBRATION WARNING
NOT SEL
[default]
WARNING
Selecting WARNING will configure
PumpSmart to issue a Keypad or DCS
notice and will trigger a Relay Output
(if configured). No further action is
taken.
23.03
SENSOR 1 MAX VAL
0-2.00 IPS
1.00 IPS
[default]
No change to this parameter is normally
required if using the STI CMCP420VT
vibration transmitter from Goulds
Pumps
23.04
SENSOR 2 MAX VAL
0-2.00 IPS
1.00 IPS
[default]
No change to this parameter is normally
required if using the STI CMCP420VT
vibration transmitter from Goulds
Pumps
23.05
WARNING LIMIT
0-1.00 IPS
.16 IPS
[default]
PumpSmart will issue a warning, based
on parameter setting 23.02, on the
Keypad if this value has been exceeded
for 20 seconds.
23.06
ALARM LIMIT
0-1.00 IPS
.22 IPS
[default]
PumpSmart will issue a alarm, based on
parameter setting 23.01, on the Keypad
if this value has been exceeded for 20
seconds.
GENERAL CONDITION
General conditions are configured in the same basic fashion as the 4-20 mA vibration transmitters. Any open
analog input channel, except AI2, may be used for GENERAL CONDITION.
Example: If a pump is being operated in basic single pump process, then the primary process transmitter is wired
through analog input channel AI2. If no vibration transmitter is being used, the GENERAL CONDITION transmitter
(e.g. temperature) could be wired into AI3 and configured as such in PumpSmart.
Parameter
Name
Value/Range
NOTES
17.20
17.22
18.01
18.02
AI1 CONFIG
AI3 CONFIG
XT AI1 CONFIG
XT AI2 CONFIG
CONDITION 1
CONDITION 2
Any unused analog input channel
(exception AI2) may be used for the
CONDITION signal. The optional RAIO-
01 AI module is required for XTAI1 and
XTAI2.
23.09
23.13
COND 1WARN LIMIT
COND 2 WARN LIMIT
0-100%
PumpSmart will issue a warnings based
on these parameter settings. The
warning value is based upon the
percentage of full scale of the
transmitter.
23.10
23.14
COND 1 ALARM LIMIT
COND 2 ALARM LIMIT
0-100%
PumpSmart will issue alarms and/or
faults based on these parameter
settings. The alarm value is based upon
the percentage of full scale of the
transmitter.
23.07
23.11
COND 1 ALARM
COND 2 ALARM
DISABLED
[default]
ALARM
FAULT
Selecting ALARM will configure
PumpSmart to issue a Keypad or DCS
notice and will trigger a Relay Output
(if configured).
If FAULT is selected, the drive will also
stop the pump.
23.08
23.12
COND 1 WARNING
COND 2 WARNING
DISABLED
[default]
WARNING
Selecting WARNING will configure
PumpSmart to issue a Keypad or DCS
notice and will trigger a Relay Output
(if configured). No further action is
taken.
Summary of Contents for PumpSmart PS200
Page 1: ... PUMPSMART CONTROL SOLUTIONS PS200 Version 4 0 Configuration Operation Guide ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 26: ......
Page 72: ......
Page 105: ......
Page 119: ......
Page 146: ...PS200 Configuration Operation Guide APPENDIX A 3 PARAMETER LISTING Page 143 ...
Page 147: ......
Page 158: ......