PS200 Configuration & Operation Guide
APPENDIX A-3 PARAMETER LISTING
Page 117
PUMPSMART ACTUAL SIGNALS
Speed C
ontr
ol
Single Pum
p
Multi-pum
p
Group 01
VFD ACTUAL SIGNALS
Description
X
X
X
1.02
MOTOR SPEED
Calculated motor speed , RPM
X
X
X
1.03
MOTOR FREQUENCY
Calculated VFD output frequency, Hz
X
X
X
1.04
MOTOR CURRENT
Measured Motor Current, A
X
X
X
1.05
MOTOR TORQUE
Calculated Motor Torque, %. 100% is the motor nominal torque
X
X
X
1.06
MOTOR POWER
Motor Power, %. 100% is the motor nominal power
X
X
X
1.07
DC BUS VOLTAGE
Measured intermediate circuit voltage, V
X
X
X
1.08
MAINS VOLTAGE
Calculated supply voltage, V
X
X
X
1.09
MOTOR VOLTAGE
Calculated motor voltage, V
X
X
X
1.10
VFD TEMP
VFD Temp, Deg C
X
X
X
1.14
OP HRS SINCE RST
Elapsed time counter; runs when the RMIO board is powered, Hrs (since last
reset). Re-settable by parameter 26.05.
X
X
X
1.15
KWH SINCE RST
kWh counter, kWh (since last reset). Re-settable by parameter 26.05.
X
X
X
1.17
DI7-1 STATUS
Status of digital inputs. Example: 1000000= DI 1L is on, DI1-DI6 are off
X
X
X
1.18
AI1[V]
Value of analog input 1, V
X
X
1.19
AI2[MA] PROC FDBK
Value of analog input 2, mA
X
X
X
1.20
AI3[MA]
Value of analog input 3, mA
X
X
X
1.21
RO3-1 STATUS
Status of relay outputs. Example: 0000001=RO1 is energized, RO2 & RO3 are de-
energized
X
X
X
1.22
AO1[MA]
Value of analog output 1, mA
X
X
X
1.23
AO2[MA]
Value of analog output 2, mA
X
X
X
1.28
XT AO1 [MA]
Value of analog output 1, mA of the Analog I/O Module (RAIO-01) – optional
X
X
X
1.29
XT AO2 [MA]
Value of analog output 2, mA of the Analog I/O Module (RAIO-01) – optional
X
X
X
1.37
MOTOR TEMP EST
Estimated motor temperature, Deg C
X
X
X
1.38
XT AI1 [MA]
Value of analog input from AI1, mA of the Analog I/O Module (RAIO-01) –
optional
X
X
X
1.39
XT AI2 [MA]
Value of analog input from AI2, mA of the Analog I/O Module (RAIO-01) –
optional
X
X
X
1.43
MOTOR RUN TIME
Motor run time counter, Hrs (since last reset). The counter runs when the inverter
modulates. Re-settable by parameter 26.05.
X
X
X
1.44
FAN ON-TIME
Fan Operating hrs. Resettable by parameter 145.13 if fan is replaced.
Speed C
ontr
ol
Single Pum
p
Multi-pum
p
Group 02
PUMP ACTUAL SIGNALS
Description
X
X
2.01
Flow Ref
Setpoint for flow control (if parameter 15.01AI2 UNIT is Gpm, M3/hr, Kg/hr,
lbm/sec or lbm/min)
X
X
2.02
Flow Actual
Actual flow feedback (if parameter 15.01AI2 UNIT is Gpm, M3/hr,Kg/hr, lbm/sec
or lbm/min)
X
X
2.03
Press Ref
Setpoint used for pressure or level control (if parameter 15.01AI2 UNIT is Psig,
Bar, M, Ft, In or Cm)
X
X
2.04
Press Actual
Actual pressure or level feedback (if parameter 15.01AI2 UNIT is Psig, Bar, M, Ft,
In or Cm)
X
X
2.05
Process Temp Ref
Setpoint used for temperature control (if parameter 15.01AI2 UNIT is F deg or C
deg)
X
X
2.06
Process Temp Act
Actual temperature feedback (if parameter 15.01AI2 UNIT is F deg or C deg)
X
X
X
2.07
Pump Speed
Actual speed of motor, Rpm
X
X
2.08
Specific Gravity
Specific Gravity of pumped liquid.
X
X
X
2.09
Wire to Water Power
Overall hp includes pump, motor and VFD,
X
X
X
2.10
Setpoint #1
Setpoint #1; unit determined by parameter 15.01AI2 UNIT
X
X
X
2.11
Setpoint #2
Setpoint #2; unit determined by parameter 15.01AI2 UNIT
X
X
X
2.12
Energy Savings
Calculated PS200 savings (option 1 or 2) since last reset. Savings are compared to
conventional system ($ or Euro). Re-settable by parameter 26.05.
X
X
X
2.13
Vibration Lvl #1
Vibration level (in/sec or mm/sec)
X
X
X
2.14
Vibration Lvl #2
Vibration level (in/sec or mm/sec)
X
X
X
2.15
Condition Lvl #1
Condition level in % of sensor FS value
X
X
X
2.16
Condition Lvl #2
Condition level in % of sensor FS value
X
X
X
2.17
Proc XT2
Current value of Process Transmitter 2 (Multivariable Control Feature)
X
X
X
2.18
PWM Signal
Current value of PWM Transmitter (Pump Wear Monitor)
Summary of Contents for PumpSmart PS200
Page 1: ... PUMPSMART CONTROL SOLUTIONS PS200 Version 4 0 Configuration Operation Guide ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 26: ......
Page 72: ......
Page 105: ......
Page 119: ......
Page 146: ...PS200 Configuration Operation Guide APPENDIX A 3 PARAMETER LISTING Page 143 ...
Page 147: ......
Page 158: ......