PS200 Configuration & Operation Guide
APPENDIX A-3 PARAMETER LISTING
Page 141
Speed C
ontr
ol
Single Pum
p
Multi-pum
p
Group 52
STD MODBUS
Settings for standard Modbus (RMBA) Link. See chapter on fieldbus control
in ABB manual.
Group 52 is unlocked when Std Modbus is selected in parameter 30.01
X
X
X
52.01
STATION NUMBER
Defines the address of the device. Two units with the same address are not
allowed on-line. 1 – 247 Default =1
X
X
X
52.02
BAUD RATE
Defines the transfer rate of the link. 600 (default), 1200, 2400, 4800, 9600 and
19200 bit/sec
PARITY
Defines the use of parity and stop bit(s). The same setting must be used on all on-
line stations.
ODD
Odd parity indication, one stopbit (Default)
EVEN
Even parity indication, one stopbit
NONE1STOPBIT
No parity bit, one stop bit
X
X
X
52.03
NONE2STOPBIT
No parity bit, two stop bits
Speed C
ontr
ol
Single Pum
p
Multi-pum
p
Group 70
DDCS CONTROL
Description
Settings for fiber optic channels 0, 1, and 3
X
X
X
70.01**
CHANNEL 0 ADDR
Defines the node address for channel 0.No two nodes on-line may have the same
address.
X
X
X
70.02**
CHANNEL 3 ADDR
Defines the node address for channel 3.No two nodes on-line may have the same
address.
X
X
X
70.03**
CHANNEL 1 BAUD RATE
Default: 2 mbits/sec
X
X
X
70.04**
DDCS CH 0 HW CONN
Default: RING
Speed C
ontr
ol
Single Pum
p
Multi-pum
p
Group 90
D SET REC ADDR
Description
Addresses of the parameters into which the received Fieldbus data are written.
Refer to the Fieldbus Control section of the ABB manual and specific Fieldbus
adapter manual for details on Fieldbus addressing.
X
X
X
90.01
MAIN DS REF2
Selects the address into which the value of Fieldbus reference Ref 2 is written.
X
X
X
90.02
AUX DS REF3
Selects the address into which the value of Fieldbus reference Ref 3 is written.
X
X
X
90.03
AUX DS REF4
Selects the address into which the value of Fieldbus reference Ref 4 is written.
X
X
X
90.04
AUX DS REF5
Selects the address into which the value of Fieldbus reference Ref 5 is written.
X
X
X
90.05
MAIN DS SOURCE
Defines the data set from which the PS200 reads the control word, reference Ref
1 and reference Ref 2.
X
X
X
90.06
AUX DS SOURCE
Defines the data set from which the PS200 reads, references Ref 3, Ref 4 and Ref
5.
Speed C
ontr
ol
Single Pum
p
Multi-pum
p
Group 92
D SET TR ADDR
Description
Main and auxiliary data sets which the PS200 sends to the Fieldbus master
station. Refer to the Fieldbus Control section of the ABB manual and specific
Fieldbus adapter manual for details on Fieldbus addressing.
X
X
X
92.01
MAIN DS STATUS WORD
Stores the address from which the Main Status Word is read from. This is a fixed
value and is not visible or accessible to the user.
X
X
X
92.02
MAIN DS ACT1
Selects the address from which the Actual Signal 1 is read to the main data set.
X
X
X
92.03
MAIN DS ACT2
Selects the address from which the Actual Signal 2 is read to the main data set.
X
X
X
92.04
AUX DS ACT3
Selects the address from which the Actual Signal 3 is read to the auxiliary data
set.
X
X
X
92.05
AUX DS ACT4
Selects the address from which the Actual Signal 4 is read to the auxiliary data
set.
X
X
X
92.06
AUX DS ACT5
Selects the address from which the Actual Signal 5 is read to the auxiliary data
set.
Summary of Contents for PumpSmart PS200
Page 1: ... PUMPSMART CONTROL SOLUTIONS PS200 Version 4 0 Configuration Operation Guide ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 26: ......
Page 72: ......
Page 105: ......
Page 119: ......
Page 146: ...PS200 Configuration Operation Guide APPENDIX A 3 PARAMETER LISTING Page 143 ...
Page 147: ......
Page 158: ......