PROCESS VARIABLE SELECTION
The process variable unit selection identifies what units
your operating mode is in. This parameter sets the units
that are used in the actual signal and setpoint display.
The defaults are shown for ENGLISH [AM] selection.
Operating Mode
Available Units Selection
Pressure
PSIG [default]
BAR
FT– Feet
M– Meters
%
Flow
GPM – Gallons Per Minute [default]
M3Hr – Cubic meters per hour
LBM/SEC - Pounds mass per second
LBM/HR - Pounds mass per hour
KG/HR - Kilograms per hour
%
Level
PSIG
BAR
FT-Feet [default]
IN - Inches
CM - Centimeters
M– Meters
%
Temperature
°F – Degrees Fahrenheit [default]
°C – Degrees Celsius
NOTE - If you are using a differential pressure flowmeter,
please see the OPTIONS & FEATURES section for assistance in
selecting the correct process variable.
15.01 AI2 UNIT
KEY SEQUENCE
[From parameter 11.03 MODE SELECT]
OR
Scroll to parameter group
15 PROCESS VAR UNIT.
Parameter 15.01 will be
the first selection
Select the proper units
of the operating mode.
Skip to the next step if
the default unit is okay,
otherwise select:
ENTER
Press to enter the
parameter setting mode
OR
Scroll to the appropriate
measurement units.
Example shown is PSIG
BAR
GPM
PSIG
(Default)
M3/HR
LBM/SEC
LBM/HR
KG/HR
%
FT
IN
CM
M
q
F
q
C
ENTER
Press to complete the
entry
NOTE - FOR PRESSURE/LEVEL MODES
If units of FT, IN, M or CM are used and Specific Gravity [SG]
is other than 1.0, parameter 17.04 must be completed. See
Options & Features.
NOTE - FOR PRESSURE/LEVEL MODES
If units of FT, IN, M or CM are used, Specific Gravity [SG] must
be constant. If SG varies widely, use units of PSIG or Bar.
ACT
PAR
FUNC
DRIVE
ENTER
1 L
Æ
0 G P M 0
1 5 P R O C E S S V A R U N I T
1 A I 2 U N I T
PSIG
AI2 refers to the Analog Input
channel No. 2. This is where your
primary process transmitter should
be physically connected
Summary of Contents for PumpSmart PS200
Page 1: ... PUMPSMART CONTROL SOLUTIONS PS200 Version 4 0 Configuration Operation Guide ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 26: ......
Page 72: ......
Page 105: ......
Page 119: ......
Page 146: ...PS200 Configuration Operation Guide APPENDIX A 3 PARAMETER LISTING Page 143 ...
Page 147: ......
Page 158: ......