PS200 Configuration & Operation Guide
SPEED CONTROL CONFIGURATION
Page 68
2.
ALARM only - In this response, PumpSmart will simply issue an
alarm/warning, but continue to operate. The alarm only mode
may result in damage to the pump if a protection limit fault
occurs.
25.06 SECONDARY PRTCT A
KEY SEQUENCE
[From parameter group 16.04 AI2 MIN]
OR
Scroll to parameter group
25 PUMP PROTECT
OR
Scroll to parameter group
25.06 SECONDARY PRTCT
A
ENTER
Press to enter the
parameter setting mode
OR
Scroll to the desired
response mode
Secondary Protect A
utilizes a process switch
into connection DI-4 to
warn of no-flow
conditions. Once wired,
select:
ALARM & CONTROL
ALARM
ENTER
Press to complete the
entry
Recommended Step:
Parameter Upload
See KEYPAD USE
Save your parameters in the keypad. In the unlikely event
that the PS200 parameters are lost, the keypad can be used
to restore the configuration. It can also be used to program
sister units that use the same or similar program settings.
!
Recommended Option:
Drive Locking
See OPTIONS & FEATURES
The keypad can be "locked" to prevent unauthorized
personnel from making operational changes or changes to
the parameter groups. See LOCKING in OPTIONS &
FEATURES.
ACT
PAR
FUNC
DRIVE
ENTER
1 L
Æ
1 0 0 0 R P M 0
2 5 P U M P P R O T E C T
6 S E C O N D A R Y P R T C T A
A L A R M & C O N T R O L
Summary of Contents for PumpSmart PS200
Page 1: ... PUMPSMART CONTROL SOLUTIONS PS200 Version 4 0 Configuration Operation Guide ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 26: ......
Page 72: ......
Page 105: ......
Page 119: ......
Page 146: ...PS200 Configuration Operation Guide APPENDIX A 3 PARAMETER LISTING Page 143 ...
Page 147: ......
Page 158: ......