ID MAGN REQ
This warning is normal, proceed on to the step
INDENTIFICATION RUN
IDENTIFICATION RUN
PumpSmart uses specific motor detail to create a
mathematical motor model. This model enables more
accurate motor control and is created with the motor data
you have just entered and by magnetizing the motor for 20
to 60 seconds at zero speed. This is called a First Start ID Run.
Once all the motor data has been entered, the following
warning will be displayed:
ID MAGN REQ
This warning indicates that a First Start ID Run is required
before the pump may be operated. Now is a good time to
perform this run.
With the motor connected to the drive and the keypad in
Local (L) mode, press the START button. FOLLOW ALL
STANDARD SAFETY PRACTICES FOR STARTING MACHINERY.
NOTE
ALLOW THE FIRST START ID RUN TO COMPLETE BEFORE
STOPPING/RESETTING THE DRIVE. Although the motor may
not appear to respond to the start command, it has. A
warning message “ID MAGN” will be displayed during the ID.
Once the ID run is complete, the message "ID DONE" will be
displayed.
NOTE - If the motor is changed in the future, a First Start ID
Run must be performed again to maintain the accuracy of the
PumpSmart control.
Once the First Start ID Run has been completed, the following
message will appear:
ID DONE
Once this appears, proceed on to the next step, DRIVE
OPERATION LIMITS.
E-Stop/Permissive
The PS200 will not operate unless
the E-Stop/Permissive switch [DI1L]
is closed. This includes performing
the First Start ID Run. If not closed
a warning message will appear on
the keypad display:
R U N D I S A B L E D
See Appendix A-4, Instrument
Wiring, for details on wiring this
switch.
NOTE:
The E-Stop/Permissive switch can not
be defeated through parameter
setting. If your application does not
use an E-Stop / Permissive switch, DI1L
can be bypassed physically inside the
PumpSmart unit. Refer to Appendix A-
4, Instrument Wiring, for details.
Summary of Contents for PumpSmart PS200
Page 1: ... PUMPSMART CONTROL SOLUTIONS PS200 Version 4 0 Configuration Operation Guide ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 26: ......
Page 72: ......
Page 105: ......
Page 119: ......
Page 146: ...PS200 Configuration Operation Guide APPENDIX A 3 PARAMETER LISTING Page 143 ...
Page 147: ......
Page 158: ......