PS200 Configuration & Operation Guide
OPTIONS & FEATURES
Page 73
Analog I/O Extension
If there are insufficient channels available on the PumpSmart drive for either vibration or general conditions,
additional channels can be added using the optional RAIO-01 module. This module adds two analog inputs and
outputs.
Parameter
Name
Value/Range
NOTES
18.01
18.02
XT AI1 CONFIG
XT AI2 CONFIG
CONDITION 1
CONDITION 2
VIBRATION 1
VIBRATION 2
NOT USED
[default]
30.02
AI/O MODULE
NO [default]
RAIO - Slot 1
RAIO - Slot 2
This parameter setting acknowledges
the presence and location of the RAIO-
01 module.
Auto Restart
The PumpSmart drive can be configured to start automatically following a power failure. Changing the value to
ON will enable auto-restart. Selecting OFF disables the auto-restart.
AUTO RESTART is also used with ERROR RESET for automatic restarts following a shutdown due to a pump protect
fault. AUTO RESTART will also restart the pump once a secondary protection fault is reset. See "Minimum Speed
Options".
Parameter
Name
Value/Range
Note
12.02
AUTO RESTART
OFF
[default]
ON
OFF
Condition Monitoring
The PS200 can monitor the mechanical condition of the pump and issue alarms and/or stop the pump in the event
of an undesired operating condition. Monitoring is performed via the analog input channels that are available on
the drive and through the optional RAIO-01 Analog I/O Extension module.
The PS200 may accommodate up to four (4) 4-20 mA signals for use as condition monitors. Two of these signals
are dedicated for vibration (Overall-RMS) and two are general signals scaled as a percentage of the transmitters
full range.
Primary
Secondary
Bearing Vibration
(IPS RMS)
VIBRATION 1
VIBRATION 2
General Condition
(% of 20mA Signal)
CONDITION 1
CONDITION 2
The general condition signals could be bearing housing temperature, additional vibration signals, or auxiliary
process conditions.
BEARING VIBRATION
Monitoring of overall pump vibration may be accomplished on the PS200 using the optional STI Vibration
Transmitter. This transmitter sends a 4-20 mA signal which corresponds to an overall RMS vibration of 0-1 Inches
Per Second (IPS). Connection of the transmitter may be made into any open input channel, except AI-2. See the
appendix for complete wiring details.
Default settings on the PS200 result in a WARNING issued at .16 IPS, and an ALARM at .22 IPS. These levels may be
adjusted up or down through parameters 23.05 and 23.06 respectively.
BEARING VIBRATION (CONT.)
A WARNING is a basic visual notification on the PumpSmart keypad display. An ALARM will also display on the
PumpSmart keypad display, but may also be configured to shut the pump down. Relay outputs [RO1, RO2, RO3]
can also be configured to activate an external sonic or visual alarm.
Summary of Contents for PumpSmart PS200
Page 1: ... PUMPSMART CONTROL SOLUTIONS PS200 Version 4 0 Configuration Operation Guide ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 26: ......
Page 72: ......
Page 105: ......
Page 119: ......
Page 146: ...PS200 Configuration Operation Guide APPENDIX A 3 PARAMETER LISTING Page 143 ...
Page 147: ......
Page 158: ......