PS200 Programming & Operation Guide
APPENDIX A-5 QUICK REFERENCE INSTALLATION DRAWINGS
Page 147
Fiber-Optic Connections between PS200 Controllers
SYNCHRONOUS MULTI-CONTROLLER AND BACKUP MODES ONLY
Constant Speed Slave Pump Wiring
ONE PUMPSMART UNIT WITH UP TO THREE CONSTANT SPEED PUMPS/STARTERS
PS200 - ACS800 Multi-Pump Connections
2-Drive Arrangement
CH-2
Multi-Pump
(MSTR-FOLL)
RDCO-03 Module
Partial View
CH-1
(I/O)
CH-3
(PC-Connect)
CH-2
Multi-Pump
(MSTR-FOLL)
RDCO-03 Module
Partial View
CH-1
(I/O)
CH-3
(PC-Connect)
Drive 1
(MASTER)
Drive 2
3-Drive Arrangement
CH-2
Multi-Pump
(MSTR-FOLL)
RDCO-03 Module
Partial View
CH-1
(I/O)
CH-3
(PC-Connect)
CH-2
Multi-Pump
(MSTR-FOLL)
RDCO-03 Module
Partial View
CH-1
(I/O)
CH-3
(PC-Connect)
CH-2
Multi-Pump
(MSTR-FOLL)
RDCO-03 Module
Partial View
CH-1
(I/O)
CH-3
(PC-Connect)
Drive 1
(MASTER)
Drive 2
Drive 3
4-Drive Arrangement
CH-2
Multi-Pump
(MSTR-FOLL)
RDCO-03 Module
Partial View
CH-1
(I/O)
CH-3
(PC-Connect)
CH-2
Multi-Pump
(MSTR-FOLL)
RDCO-03 Module
Partial View
CH-1
(I/O)
CH-3
(PC-Connect)
CH-2
Multi-Pump
(MSTR-FOLL)
RDCO-03 Module
Partial View
CH-1
(I/O)
CH-3
(PC-Connect)
CH-2
Multi-Pump
(MSTR-FOLL)
RDCO-03 Module
Partial View
CH-1
(I/O)
CH-3
(PC-Connect)
Drive 1
(MASTER)
Drive 2
Drive 3
Drive 4
Fiber Optic Cables
-Light colored connector to light
colored receptical.
-Dark colored connector to dark
colored receptical
-MINIMUM BEND RADIUS: 2 Inches
Extra cable may be looped and stored
within the drive. Maintain minimum
bend radius.
Fiber optic cable ends are not the same
color.
Fiber Optic Cable Kit
Part Numbers
2 Pumps - 800MP2
3 Pumps - 800MP3
4 Pumps - 800MP4
The RDCO-03 DDCS
COMMUNICATION
MODULE is to be mounted
in the DDCS slot and affixed
with (2) screws provided
Copyright 2004 ITT Industries
RO1 (X25) Slave 1
RO2 (X26) Slave 2
RO3 (X27) Slave 3
Relay Output Specifications
Switching Capacity
8A at 24 VDC or 250 VAC
0.4A at 120 VDC
Maximum Continuous Current:
2 A RMS
START/STOP
By Customer
Control Loop
Power Source
ON/OFF
E-Stop
PS200 Form C Relays
SLAVE MOTOR
STARTER
T1
T2
T3
Slave Motor
Power
Supply
1 RO NC
2 RO COM
3 RO NO
OP
TI
ON
ASSIGNABLE RELAY OUTPUT
PARAMETERS 19.01, 19.04,
AND/OR 19.07 SET TO "START
SLAVE"
B05027A
SHEET 1 OF 1
REV
0
Issue
-
PS 200 ACS 800 Multipump
Connections V4.0
Drawing is not to scale
Dimensions in inches [mm]
Checked: Tony Stavale
Drawn: AI 060204
PS200
X21
X22
X23
X25
X26
X27
X20
!! NOTE !!
y
PumpSmart issues run commands to constant speed slave units via relay output run (2-wire
start/stop).
y
Control loop must be powered (e.g. 24 VDC or 120 VAC.
y
The default starting order for multiple constant speed slave units is:
y
RO1 - Starts/stops first constant speed slave pump. Destages pump using the 22.07
SYNC LIMIT.
y
RO2 - Starts/stops the second constant speed slave pump. Destages this pump using
22.07 SYNC LIMIT and 22.08 SYNC WINDOW
y
RO3 - Starts/stops the third constant speed slave pump. Destages this pump using
22.07 SYNC LIMIT and 2x 22.08 SYNC WINDOW
Summary of Contents for PumpSmart PS200
Page 1: ... PUMPSMART CONTROL SOLUTIONS PS200 Version 4 0 Configuration Operation Guide ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 26: ......
Page 72: ......
Page 105: ......
Page 119: ......
Page 146: ...PS200 Configuration Operation Guide APPENDIX A 3 PARAMETER LISTING Page 143 ...
Page 147: ......
Page 158: ......