PS200 Configuration & Operation Guide
APPENDIX A-3 PARAMETER LISTING
Page 140
Speed C
ontr
ol
Single Pum
p
Multi-pum
p
Group 30
OPTION MODULES
Description
FIELDBUS
Activates the optional external DCS and selects the interface. Refer to the ABB
IOM chapter on Fieldbus control.
NO
[default]
No Fieldbus communication
FIELDBUS
The drive communicates with a Fieldbus adapter module in option Slot 1 or via
CH 0 Fieldbus adapter link. Note when “Fieldbus” is selected Parameter Groups
31, 90 and 92 are unlocked.
ADVENT
The drive communicates with an ABB Advent OCS System via channel 0 on the
RDCO board. Note when “Advent” is selected, parameter Groups 31, 90, and 92
are unlocked.
X
X
X
30.01
STD MODBUS
The drive communicates with a Modbus controller via the Modbus Adapter
Module (RMBA) in option Slot 1 of the drive. Note when “Std Modbus” is
selected, parameter Groups 31, 52, 90, and 92 are unlocked.
AI/O EXT MODULE
Activates the communication to an optional RAIO-01 I.O analog extension
module. Required for XTAI1, XTAI2 and/or analog outputs 3 and 4
NO
[default]
No RAIO analog extension module is active
X
X
X
30.02
RAIO SLOT 1
RAIO SLOT 2
An RAIO analog extension module is connected and active in Slot 1.
An RAIO analog extension module is connected and active in Slot 2.
X
X
X
30.03
COMM PROFILE
This parameter becomes visible if FIELDBUS or STD MODBUS is selected in 30.01
FIELDBUS. This defines the profile on which the communication with the fieldbus
is based. Default: CSA2.8/3.0. Other choices are ABB DRIVES and GENERIC. For
LonWorks, use GENERIC setting.
X
X
X
30.04**
EXT AI1 FUNC.
Default = UNIPOLAR, Other choice is BIPOLAR
X
X
X
30.05**
EXT AI2 FUNC.
Default = UNIPOLAR, Other choice is BIPOLAR
Speed C
ontr
ol
Single Pum
p
Multi-pum
p
Group 31
FIELDBUS SETUP
Description
X
X
X
31.01
MODULE TYPE
This parameter configures the module type automatically by the fieldbus adapter.
No action is required unless changes to default settings are desired. Refer to the
fieldbus manual. This parameter becomes visible when “FIELDBUS” is selected in
parameter 30.01 FIELDBUS.
Speed C
ontr
ol
Single Pum
p
Multi-pum
p
Group 50
MOTOR CONTROL
Speed Controller & Other Motor Variables
These functions are not used when in Scalar Mode
X
X
X
50.01**
GAIN
Defines a relative gain for the speed controller. Great gain may cause speed
oscillation.
X
X
X
50.02**
INTEGRATION TIME
Defines an integration time for the speed controller.
X
X
X
50.03**
DERIVATION TIME
Defines a derivation time for the speed controller.
X
X
X
50.04**
ACC COMPENSATION
Defines a derivation time for acceleration compensation.
X
X
X
50.05**
SLIP GAIN
Defines the slip gain for the motor slip compensation control.
X
X
X
50.06**
AUTOTUNE RUN
Start automatic tuning of the speed controller. Default = NO.
X
X
X
50.07**
FLUX OPTIMIZATION
Activates/Deactivates the flux optimization function. Default = NO.
X
X
X
50.08**
FLUX BREAKING
Activates/Deactivates the flux breaking function. Default = YES.
X
X
X
50.09**
MOTOR SP FILT TIME
Defines a filter time constant for the actual signal speed.
X
X
X
50.10**
TORQUE ACT FILT TIM
Defines a filter time constant for the actual signal torque.
X
X
X
50.11**
RESET RUN TIME
Resets the motor running time counter. Default = NO.
X
X
X
50.12**
START FUNCTION
Selects the motor starting method. Default = DC MAGN. Other choices:
CONSTANT DC MAGN, AUTO.
X
X
X
50.13**
CONST MAGN TIME
Defines the magnetizing time in the constant magnetizing mode
X
X
X
51.03**
IR-COMPENSATION
Defines the relative output voltage boost at zero speed (IR Compensation). Useful
in applications with high breakaway torque. Used in Scalar Control only.
X
X
X
51.05**
HEX FIELD WEAKEN
NO (default), YES
Summary of Contents for PumpSmart PS200
Page 1: ... PUMPSMART CONTROL SOLUTIONS PS200 Version 4 0 Configuration Operation Guide ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 26: ......
Page 72: ......
Page 105: ......
Page 119: ......
Page 146: ...PS200 Configuration Operation Guide APPENDIX A 3 PARAMETER LISTING Page 143 ...
Page 147: ......
Page 158: ......