PS200 Configuration & Operation Guide
APPENDIX A-3 PARAMETER LISTING
Page 135
Speed C
ontr
ol
Single Pum
p
Multi-pum
p
Group 23
CONDITION SETUP
Description
COND 2 WARNING
% Setting above 23.13 for greater than 20 sec. Note: parameter 30.02 AI/O EXT
MODULE must be set to “YES” if RAIO-01 module is used.
DISABLED
[default]
Protection is inactive. Default
X
X
X
23.12
WARNING
The PS200 displays the message "COND 2 HIGH". Relay output(s) may be
configured to change. No further action is taken.
X
X
X
23.13
COND 2 WARN LIMIT
Range is 0 – 100% of FS sensor value. This is the lower warning limit. Default is
100%
X
X
X
23.14
COND 2 ALRM LIMIT
Range is 0 – 100% of FS sensor value. This is the upper alarm limit. Default is
100%
Speed C
ontr
ol
Single Pum
p
Multi-pum
p
Group 24
FAULT FUNCTIONS
Description
PROC SNSR FAILURE
Selects the PS200 reaction when Ext SP, Proc XT1, Spd Ref or Proc XT2 analog
signal falls below 1.5V / 3 mA or above 10.1V / 20.2 mA for 2 seconds. The sensor
failure warning is identified as to which particular sensor has failed based on the
analog input configuration settings given in parameters 17.20, 17.21 and 17.22.
DISABLED
Protection is inactive
FAULT
The drive trips on fault and the motor coasts to a stop. A fault message is
generated “EXT SP, PROC XT1, SPD REF or PROC XT2” Err.
X
X
X
24.01
LAST SPEED
[default]
)
The drive generates a warning “EXT SP, PROC XT1, SPD REF or PROC XT2 ERR” and
freezes the speed to the average speed the drive was operating at over the last 60
seconds.
COND SNSR FAILURE
Selects how the PS200 will react when Cond 1, Cond 2, Vib 1, Vib 2 or PWM
signal falls below 1.5V / 3 mA or above 10.1V / 20.2 mA for 2 seconds. The sensor
failure warning is identified as to which particular sensor has failed based on the
analog input configuration settings given in parameters 17.20, 17.22, 18.01 and
18.02.
DISABLED
Protection is inactive
X
X
X
24.02
WARNING
[default]
The PS200 generates a warning “COND 1, COND 2, VIB 1, VIB 2 or PWM SGNL
ERR".
KEYPAD FAILURE
Selects how the PS200 will react to a keypad communication break.
DISABLED
Protection is inactive
FAULT
The drive trips on fault and the motor coasts to a stop. A fault message is
generated “PANEL LOSS”. If an external start/stop switch is used and the
reference is sent via analog input, no fault will occur if the keypad fails.
X
X
X
24.03
LAST SPEED
[default]
The drive generates a warning “PANEL LOSS” and freezes the speed to the
average speed the drive was operating at over the last 60 seconds.
Summary of Contents for PumpSmart PS200
Page 1: ... PUMPSMART CONTROL SOLUTIONS PS200 Version 4 0 Configuration Operation Guide ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 26: ......
Page 72: ......
Page 105: ......
Page 119: ......
Page 146: ...PS200 Configuration Operation Guide APPENDIX A 3 PARAMETER LISTING Page 143 ...
Page 147: ......
Page 158: ......