PS200 Configuration & Operation Guide
SINGLE PUMP PROCESS
Page 17
PROCESS TRANSMITTER CONFIGURATION
The primary process transmitter is the device that will measure
your process conditions. The PS200 requires information to
properly scale the 4-20 mA signal that the transmitter sends.
AI2 MAX - This refers to the process value that your transmitter is
calibrated to at its max signal [20 mA]. Refer to your transmitter
calibration sheet, or the instrument nameplate, for this value.
Example - a direct reading flowmeter [e.g. magmeter, vortex
flowmeter, etc…] that has a range of 0 - 2000 GPM would
be calibrated such that at 2000 GPM, the output of the
transmitter would be 20 mA. Parameter 16.03 would be set
to 2000 in this case. The units of 16.03 are the same as
selected in parameter 15.01.
NOTES
Differential pressure flowmeters [e.g. orifice plate, venturi] do
not produce 4-20 mA signals that are linear with the flow-
rate. PumpSmart refers to this as a QUADRATIC input -- Refer
to the section DIFFERENTIAL PRESSURE FLOWMETERS in the
options section for proper setup.
16.03 AI2 MAX
KEY SEQUENCE
[From parameter group: 15.01 AI2 UNIT]
OR
Scroll to parameter group
16 SETPOINT SELECT
OR
Scroll to parameter 16.03
AI2 MAX
ENTER
Press to enter the
parameter setting mode
OR
OR
Use a combination of the
arrow keys to scroll to the
correct value. Example
shown - 300 PSIG
Enter the reading of the
primary process
transmitter that
corresponds to its 20
mA signal.
Units are the same as
entered in 15.01.
ENTER
Press to complete the
entry
ACT
PAR
FUNC
DRIVE
ENTER
1 L
Æ
0 P S I G 0
1 6 S E T P O I N T S E L E C T
3 A I 2 M A X
300
Summary of Contents for PumpSmart PS200
Page 1: ... PUMPSMART CONTROL SOLUTIONS PS200 Version 4 0 Configuration Operation Guide ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 26: ......
Page 72: ......
Page 105: ......
Page 119: ......
Page 146: ...PS200 Configuration Operation Guide APPENDIX A 3 PARAMETER LISTING Page 143 ...
Page 147: ......
Page 158: ......