PS200 Configuration & Operation Guide
MULTI PUMP-PROCESS CONFIGURATION
Page 41
3
b
Multi-pump Control Settings
This section configures the PumpSmart PS200 as to how the
multiple pumps will be sequenced. There are three main
steps:
1.
Selection of operating mode
2.
Adding pumps (staging)
3.
De-staging pumps.
22.01 MULTI-PUMP CONTROL MODE -
Refer to the Multi-Pump Overview section for help with
determining which operating mode you want to use.
The most common multi-pump control mode is
SYNCHRONOUS, where lead and lag drives will operate at the
same speed.
22.01 OPERATING MODE
KEY SEQUENCE
[From parameter group 16.04 AI2 MIN]
OR
Scroll to parameter group
22, MULTI PUMP CTRL.
Parameter 22.01 will be
the first selection
ENTER
Press to enter the
parameter setting mode
OR
Scroll to the desired
control mode.
Select the multi-pump
operating mode.
If your desired operation
is SYNCHRONOUS, skip
to the next step.
Options:
SYNCHRONOUS (Default)
MULTICONTROL
CONSTANT SLV (Slave)
BACKUP
ENTER
Press to complete the
entry
CONSTANT SLAVE MODE (ONLY)
In Constant Slave mode, the PumpSmart unit activates the
constant speed slave pump using relay output(s) (e.g. RO1,
RO2 and/or RO3) These relay’s must be configured using
parameter group 19. See OPTIONS for further details.
BACKUP MODE
If backup mode is selected, skip to the setup of parameter
22.13 TX CONFIG.
ACT
PAR
FUNC
DRIVE
ENTER
1 L
Æ
0 P S I G 0
2 2 M U L T I P U M P C T R L
1 O P E R A T I N G M O D E
SYNCHRONOUS
2
4
!
1
Control Mode
Removing
Pumps
Adding Pumps
3
a
3
b
Summary of Contents for PumpSmart PS200
Page 1: ... PUMPSMART CONTROL SOLUTIONS PS200 Version 4 0 Configuration Operation Guide ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 26: ......
Page 72: ......
Page 105: ......
Page 119: ......
Page 146: ...PS200 Configuration Operation Guide APPENDIX A 3 PARAMETER LISTING Page 143 ...
Page 147: ......
Page 158: ......