PS200 Configuration & Operation Guide
SPEED CONTROL CONFIGURATION
Page 69
Starting & Stopping
The PumpSmart system is now ready to start. Starting and
stopping the PumpSmart unit is possible through the keypad
when in local control.
NOTE - The drive can also be started using a 2 or 3 wire switch or
through a Fieldbus command. To start, press the LOC-REM button
until "R" is displayed in the upper left status row. You are now
ready to start from a remote location.
KEY SEQUENCE
LOC
REM
Press LOC/REM button until "L" is displayed in the status
row
Press to start
Press to stop
Jogging the Motor for Rotation
Once the ID MAGN has been
completed, jogging the motor to
check for rotation may be performed
by scrolling to parameter 12.09
MOTOR JOG and selecting JOG. Once
selected, PumpSmart will turn the
motor at 60 RPM for 10 seconds.
If rotation is reversed, the position of
two leads must be changed either at
the drive output (U
2
, V
2
, W
2
) or at the
motor (T
1
, T
2
, T
3
). Refer to the Quick
Reference Installation drawings in the
appendix.