PS200 Configuration & Operation Guide
APPENDIX A-3 PARAMETER LISTING
Page 123
Speed C
ontr
ol
Single Pum
p
Multi-pum
p
Group 11
START UP DATA
Description
APPLIC RESTORE
Restores the original defaults of the application macro
NO
[default]
No restoring
X
X
X
11.11**
YES
Restoring
X
X
X
11.12
OTHER MOTOR VOLT
Visible if “Other” is selected in 11.04. The User inputs the voltage value.
CTRL BOARD SUPPLY
Defines the source of the control board power
INTERNAL 24
[default]
Uses internal power supply for control board
X
X
X
11.13**
EXTERNAL 24
Optional control board powering method.
Speed C
ontr
ol
Single Pum
p
Multi-pum
p
Group 12
START/STOP
Description
START/STOP
Defines the connections and source of the start/stop commands
2 WIRE /HOA
[default]
Start/Stop through DI1. 0 = stop, 1 = start. Manual override through DI-2. 0 =
No, 1 = override. After a fault reset, the drive will restart only if auto restart
(12.02) is set to on. If auto restart is off the start signal must be removed and
reapplied.
3 WIRE
Pulse start through digital input DI1. 0>1: Start. Pulse stop through digital input
2 DI2. 1>0: Stop.
X
X
X
12.01
FIELDBUS
Start via Fieldbus control word
AUTO RESTART
Selects whether the PS200 will automatically restart after a power failure.
OFF
[default]
Not selected
X
X
X
12.02
ON
Selected. The PS200 will automatically restart if conditions permit.
TEST RUN
Selects when the drive will perform a test run
NOT SEL
[default]
Not selected
AUTOMATIC
If selected and the drive has not run for the test delay (12.05) the drive will start
and run at 50% of maximum speed (14.01) for 20 seconds and shutdown. Auto
Restart 12.02 must be on.
X
X
X
12.03
MANUAL
Once manual is selected the drive will start and run at test speed for 20 seconds
and shutdown. Once the manual test is complete this parameter will return to
“NOT SEL”.
TEST SPEED % (FL)
Selects the speed the test runs at in manual test mode (12.03)
X
X
X
12.04
0 – 100%
Setting range. Default is 25% of maximum speed (14.01).
TEST RUN DELAY
Selects how long after the drive is idle before it will do a test run
X
X
X
12.05
0.1 – 3600 HR
Setting range. Default is 1000 Hr.
MANUAL OVERRIDE
Disables the control algorithm and pump protection parameters 23.01, 23.07,
23.11, 24.01, 25.01, 25.06, 25.07, 25.11, 25.13, and 25.15. Will NOT override E-
Stop/Permissive function.
OFF
[default]
Not selected
X
X
12.06
ON
Selected
MANUAL OVERRIDE RPM
Initial default is 14.02 MINIMUM SPEED. Saves the last manual override speed for
HOA function. Updates to the current process speed when 12.06 MANUAL
OVERRIDE turned-on. Does not update if using an external switch to engage
override (hand) function.
X
X
X
12.07
0 - 3600 RPM
Setting range
STOP FUNCTION
Selects how the motor should stop during normal shutdown.
RAMP
[default]
Pump shuts down using the ramp rate defined in 13.02 DECEL TIME
X
X
X
12.08
COAST
Power is cut immediately to motor allowing it to coast to a stop.
MOTOR JOG
Jogs motor for 10 sec @ 60 rpm to check for motor rotation.
DISABLED
[default]
Motor jog is not active.
X
X
X
12.09
JOG
Jogs motor for 10 sec at 60 rpm. After jog is complete this parameter setting
returns to disabled.
Summary of Contents for PumpSmart PS200
Page 1: ... PUMPSMART CONTROL SOLUTIONS PS200 Version 4 0 Configuration Operation Guide ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 26: ......
Page 72: ......
Page 105: ......
Page 119: ......
Page 146: ...PS200 Configuration Operation Guide APPENDIX A 3 PARAMETER LISTING Page 143 ...
Page 147: ......
Page 158: ......