Goodrive300-LIFT series inverter
Function parameters
-65-
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P11.10
Overload alarm
detection
time
overload alarm function.
Setting range: 0x000
–
0x131
LED ones:
0: Motor overload alarm, relative to the rated
current of the motor
1: Inverter overload alarm, relative to the rated
current of the inverter
LED tens:
0: The inverter continues working after
overload/underload alarm.
1: The inverter continues working after
underload alarm reporting but it stops
running upon an overload fault.
2: The inverter continues working after overload
alarm reporting but it stops running upon an
underload fault.
3: The inverter stops running after
overload/underload alarm reporting.
LED hundreds:
0: Detection all the time
1: Detection in constant running
Setting range of
: 100%
–
200%
Setting range of
: 0.1
–
3600.0s
1.0s
○
P11.11 Motor overload
selection
0: No protection
1: Common motor
2: Variable-frequency motor
2
◎
P11.12
Motor overload
protection
coefficient
20.0%
–
120.0%
100.0
○
P11.13 Speed deviation
detection
0.0
–
50.0%
10.0%
○
P11.14 Speed deviation
detection time
This parameter is used to set the speed
deviation detection time.
Note: Speed deviation protection is disabled
when
1.0s
○