Goodrive300-LIFT series inverter
Function parameters
-64-
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P11.07
Frequency-decre
asing ratio
during current
limit
the output current and compare it with the limit
level defined in
. If it exceeds the level,
the inverter will run at stable frequency in ACC
running, or the inverter will derate to run during
the constant running. If it exceeds the level
continuously, the output frequency will keep on
decreasing to the lower limit. If the output
current is detected to be lower than the limit
level, the inverter will accelerate to run.
Output current A
Output frequency
f
Current
limit point
Set
frequency
ACC process
Constant speed
process
Time t
Time t
Setting range of
: 50.0
–
200.0%
Setting range of
: 0.00
–
50.00Hz/s
10.00Hz
/s
◎
P11.08
Inverter/motor
overload
alarm
The output current of the inverter or the motor is
above
and the lasting time is beyond
, overload alarm will be output.
Y,
RO1, RO2
Output current
Overload alarm
point
Time t
Time t
Alarm time t
Alarm time t
: Enable and define the inverter/motor
0x000
○
P11.09 Overload alarm
detection
Model
G: 150%
○