Goodrive300-LIFT series inverter
Communication protocol
-129-
Code
Name
Meaning
the range, but indicate the message frame is an illegal frame.
04H
Operation
failed
The parameter setting in parameter writing is invalid. For example,
the function input terminal cannot be set repeatedly.
05H
Password
error
The password written to the password check address is not same as
the password set by
06H
Data frame
error
In the frame message sent by the upper monitor, the length of the
digital frame is incorrect or the counting of CRC check bit in RTU is
different from the lower monitor.
07H
Parameters
only for read
It only happen in write command
08H
Parameters
cannot be
changed
during
running
The modified parameter in the writing of the upper monitor cannot be
modified during running.
09H
Password
protection
When the upper monitor is writing or reading and the user password
is set without password unlocking, it will report that the system is
locked.
The slave uses functional code fields and fault addresses to indicate it is a normal response or some
error occurs (named as objection response). For normal responses, the slave shows corresponding
function codes, digital address or sub-function codes as the response. For objection responses, the
slave returns a code which equals the normal code, but the first byte is logic 1.
For example: when the master sends a message to the slave, requiring it to read a group of address
data of the inverter function codes, there will be following function codes:
0 0 0 0 0 0 1 1 (Hex 03H)
For normal responses, the slave responds the same codes, while for objection responses, it will
return:
1 0 0 0 0 0 1 1 (Hex 83H)
Besides the function codes modification for the objection fault, the slave will respond a byte of
abnormal code which defines the error reason.
When the master receives the response for the objection, in a typical processing, it will send the
message again or modify the corresponding order.
For example, set the "running command channel" of the inverter (
, parameter address is
0001H) with the address of 01H to 03, the command is as following: