Goodrive300-LIFT series inverter
Communication protocol
-130-
Inverter
address
Read
command
Parameter
address
Parameter
data
CRC
01
06
00 01 00 03
98 0B
But the setting range of "running command channel" is 0
–
2, if it is set to 3, because the number is
beyond the range, the inverter will return fault response message as below:
Exception
response code
Error code
CRC
01
86
04
43 A3
Inverter
address
Abnormal response code 86H means the abnormal response to writing command 06H; the fault code
is 04H. In the table above, its name is operation failed and its meaning is that the parameter setting in
parameter writing is invalid.
10.4.8 Example of writing and reading
Refer to 10.4.1 and 10.4.2 for the command format.
10.4.8.1 Example of reading command 03H
Read the state word 1 of the inverter with the address of 01H (refer to table 1). From the table 1, the
parameter address of the state word 1 of the inverter is 2100H.
The command sent to the inverter:
Inverter
address
Read
command
Parameter
address
Data quantity
CRC
01
03
21 00 00 01
8E 36
If the response message is as below:
Inverter
address
Read
command
Number of
bytes
CRC
01
03
02
00 03
F8 45
Data
content
The data content is 0003H. From the table 1, the inverter stops.
Watch "Type of current fault" to "Type of last but four fault" of the inverter through commands, the
corresponding function code is
and corresponding parameter address is
071BH
–
0720H (there are 6 from 071BH).
The command sent to the inverter:
Inverter
address
Read
command
Start
address
CRC
03
03
07 1B 00 06
B5 59
6 parameters
in total
If the response message is as below:
Inverter
address
Read
command
Type of
current fault
CRC
01 03
00 23
5F D2
Number
of bytes
0C
Type of last
fault
00 23
Type of last
but one fault
00 23
Type of last
but two fault
00 23
Type of last
but three fault
00 23
Type of last
but four fault
00 23