Goodrive300-LIFT series inverter
Fault tracking
-99-
Code
Fault
Possible cause
Solution
The keypad wire is too
long and affected by
strong interference.
There is circuit fault on
the communication of the
keypad and main board.
Check the environment and
avoid
the
interference
source.
Change the hardware and
ask for service.
UPE
Parameters
uploading fault
The connection of the
keypad wires is not good
or broken.
The keypad wire is too
long and affected by
strong interference.
Communication fault.
Check the keypad wires
and ensure whether there is
mistake.
Change the hardware and
ask for service.
Change the hardware and
ask for service.
DNE
Parameters
downloading fault
The connection of the
keypad wires is not good
or broken.
The keypad wire is too
long and affected by
strong interference.
There is mistake on the
data storage of the
keypad.
Check the keypad wires
and ensure whether there is
mistake.
Change the hardware and
ask for service.
Repack-up the data in the
keypad.
E-DP
PROFIBUS
communication fault
Communication address
is not correct.
Corresponding resistor is
not dialed
The files of main stop
GSD does not set sound
Check related setting
E-NET
Ethernet
communication fault
The Ethernet address is
not set right.
The
Ethernet
communication is not
selected to right.
The ambient interference
is too strong.
Check the relative setting.
Check the communication
method selection.
Check the environment and
avoid the interference.
E-CAN
CANopen
communication fault
The connection is not
sound
Check the connection
Draw out the correspond