What this chapter contains
This chapter describes the basic principles for the installation and commission of the inverter, which
helps you to quickly complete the installation and commissioning.
2.2
Unpacking inspection
Check the following items after receiving the product.
1. Whether the packing box is damaged or dampened.
2. Whether the model identifier on the exterior surface of the packing box is consistent with
the purchased model.
3. Whether the interior surface of the packing box is abnormal, for example, in wet condition,
or whether the enclosure of the product is damaged or cracked.
4. Whether the nameplate of the product is consistent with the model identifier on the exterior
surface of the packing box.
5. Whether the accessories (including the user manual, control keypad, and extension cards)
inside the packing box are complete.
If any of the problems described in the check items are found, contact the local dealer or our
company.
2.3
Application confirmation
Confirm the following items before using the inverter.
1. Mechanical type of the load to be drived by the inverter. Check whether the inverter will be
overloaded in actual operation and whether the power level needs to be raised.
2. Whether the actual running current of the to-be-loaded motor is lower than the rated current
of the inverter.
3. Whether control precision implemented by the inverter meets the requirement of the actual
load.
4. Whether the grid voltage is consistent with the rated voltage of the inverter.
5. Whether you need to configure an extension card to implement the required communication
mode.
2.4
Environment confirmation
Check the following items before you install and use the inverter.
1. Whether the ambient temperature in the application is higher than 40°C. If yes, derate the
machine by 3% for every increased 1°C. Do not use the inverter in environments where the
temperature is higher than 50°C.
Note:
If the inverter is installed in a cabinet, the ambient temperature is the air temperature