Goodrive300-LIFT series inverter
Commissioning guidelines
-89-
Function
code
Name
Recommended
value
Remarks
segment duration
DEC time
2.0s
S-curve start
segment duration
during stop
2.0s
S-curve end
segment duration
during stop
2.0s
Maintenance
running speed
0.200m/s
Maintenance ACC/
DEC time
4.0s
DEC time for
creeping to stop
1.0s
7.5.2 Analog tracking running
This running mode indicates that the speed command is provided by analog input, the inverter
passively runs based on the analog signal as provided, the lift running curve is determined by the
analog change curve generated by the external controller, and the inverter is responsible for driving
the motor to run. The analog tracking running input channel must be provided by AI1 (
=5).
Running sequence
The running sequence in this mode is similar to that in the multi-step speed running mode.
Note
:
•
During analog tracking running, the inverter internal S curve does not work, the S curve of lift
running is generated by the lift controller. Adjusting
analog input.
•
Great analog change ratio will cause inverter running frequency transient, which may result in
inverter overcurrent or overvoltage.
7.5.3 Maintenance running
Figure 7-9 shows the basic wiring for maintenance running.