Goodrive300-LIFT series inverter
Function parameters
-69-
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P14.08
CAN
communication
rate
0: 50 k
1: 100 k
2: 125 k
3: 250 k
4: 500 k
0
○
P14.09
CAN
communication
error time
0.0
–
10.0s
1.0
○
P14.10
Reserved
0
–
65535
0
○
P14.11
Reserved
0
–
65535
0
○
P15 Group Bluetooth communication
P15.00 Expansion card
type
0: No
1: STO
2: IO
3: Bluetooth
1
◎
P15.01
STO function
setting
0: STO alarm locked (the SAFE fault can be
reset)
Alarm locking refers to that after a SAFE fault
occurs and the state is restored, you need to
manually reset.
1: STO alarm not locked
No alarm locking refers to that after a SAFE fault
occurs and the state is restored, the alarm is
automatically deleted.
Note:
All of STL1 to STL3 faults are set to alarm
locked, and cannot be reset. After the state is
restored, you need to apply power again for
reset.
0
○
P15.02
Reserved
0
–
65535
○
P15.03
Reserved
0
–
65535
○
P15.04
Reserved
0
–
65535
○
P15.05
Reserved
0
–
65535
○
P16 Group Ethernet communication
P16.00
Ethernet
communication
speed
0: Self-adapting
1: 100M full duplex
2: 100M semiduplex
3: 10M full duplex
4: 10M semiduplex
3
◎