Goodrive300-LIFT series inverter
Function parameters
-68-
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P14.04
Communication
timeout fault
duration
0.0 (invalid), 0.1
–
60.0s
When the function code is set as 0.0, the
parameter is invalid.
When the function code is set as non-zero, if the
interval time between two communications
exceeds this parameter value, the system will
report "485 communication faults" (CE).
Generally, set it as invalid; set the parameter in
the continuous communication to monitor the
communication state.
0.0s
○
P14.05
Transmission
fault processing
0: Alarm and stop freely
1: No alarm and continue to run
2: No alarm and stop according to the stop mode
(only under the communication control)
3: No alarm and stop according to the stop mode
(under all control modes)
0
○
P14.06
Communication
processing
0x00
–
0x11
LED ones:
0: Write with response: the inverter will respond
to all reading and writing commands of the
upper monitor.
1: Write without response: the inverter only
responds to the reading command other than
the writing command of the drive. The
communication efficiency can be increased by
this method.
LED tens:
0: Communication encrypting invalid
1: Communication encrypting valid
0x00
○
P14.07
CAN
communication
address
0
–
127 (0 is a broadcast address, indicating that
messages are sent but not replied)
2
○