1.
The Error Code field (Byte 0) is set to 70h to indicate a current error,
that is one associated with the most recently received command. It is
set to 71h to indicate a deferred error which is not associated with the
current command.
2.
The segment number (Byte 1) is zero since the Copy, Compare, and
Copy and Verify commands are not supported.
3.
The File Mark flag (Byte 2, bit 7) is set if a Space, Read, or Verify
command did not complete because a file mark was read.
4.
The End of Media (EOM) flag (Byte 2, bit 6) is set if a Write or Write
File Marks command completed in the early warning area. Spacing into
BOM also causes this flag to be set. It is also set on an attempt to read
or space past EOD, or if an attempt is made to space into Beginning of
Media.
5.
The Illegal Length Indicator (ILI) flag (Byte 2, bit 5) is set if a Read or
Verify ended because a block was read from tape that did not have the
block length requested in the command.
6.
The Information Bytes (Bytes 3-5) are only valid if the Valid flag is set.
This occurs only for current errors and not for deferred errors.
7.
The Field Replaceable Unit field (Byte 14) is set to either zero or to a
non-zero, vendor-specific code indicating which part of the drive is
suspected of causing the failure.
8.
The Clean (CLN) flag (Byte 21, bit 3) is set if the drive needs cleaning
and clear otherwise.
9.
The Volume Label Fields Valid (VolValid) bit (Byte 21, bit 0) is set if the
Volume Label being reported is valid.
10.
The Volume Label field (Bytes 22-28) reports the volume label if a
cartridge is loaded in the drive and Volume Label Fields Valid is set.
11.
The Current Wrap field (Byte 29) reports the physical wrap of the tape.
The least significant bit reflects the current physical direction. A 0
means that the current direction is away from the physical beginning of
the tape. A 1 means that the current direction is towards the physical
beginning of the tape.
12.
Relative LPOS fields (Bytes 30-33) reports the current physical position
on the tape.
13.
SCSI Address field (Byte 34) reports the SCSI Bus Address for the drive.
Values returned range from 00h to 0Fh.
14.
This field (Byte 35) contains the frame and drive number, passed across
the RS-422 serial interface.
B-12
TS3310 Tape Library Maintenance Information
Summary of Contents for System Storage TS3310
Page 2: ......
Page 6: ...iv TS3310 Tape Library Maintenance Information...
Page 8: ...vi TS3310 Tape Library Maintenance Information...
Page 18: ...xvi TS3310 Tape Library Maintenance Information...
Page 20: ...xviii TS3310 Tape Library Maintenance Information...
Page 22: ...xx TS3310 Tape Library Maintenance Information...
Page 28: ...1 6 TS3310 Tape Library Maintenance Information...
Page 76: ...3 14 TS3310 Tape Library Maintenance Information...
Page 92: ...4 16 TS3310 Tape Library Maintenance Information...
Page 196: ...6 94 TS3310 Tape Library Maintenance Information...
Page 242: ...7 46 TS3310 Tape Library Maintenance Information...
Page 378: ...8 136 TS3310 Tape Library Maintenance Information...
Page 382: ...9 4 TS3310 Tape Library Maintenance Information...
Page 390: ...10 8 TS3310 Tape Library Maintenance Information...
Page 396: ...A 6 TS3310 Tape Library Maintenance Information...
Page 415: ...Library Electrical Block a66mi038 Appendix C Library Diagrams C 7...
Page 416: ...Library Control Blade a66mi042 C 8 TS3310 Tape Library Maintenance Information...
Page 417: ...Library Control Blade Functions a66mi039 Appendix C Library Diagrams C 9...
Page 418: ...Accessor Control Block a66mi040 C 10 TS3310 Tape Library Maintenance Information...
Page 421: ...a66mi036 Appendix C Library Diagrams C 13...
Page 423: ...Library Power System a66mi044 Appendix C Library Diagrams C 15...
Page 424: ...a66mi043 C 16 TS3310 Tape Library Maintenance Information...
Page 484: ...D 60 TS3310 Tape Library Maintenance Information...
Page 494: ...E 10 TS3310 Tape Library Maintenance Information...
Page 498: ...F 4 TS3310 Tape Library Maintenance Information...
Page 504: ...G 6 TS3310 Tape Library Maintenance Information...
Page 520: ...H 16 TS3310 Tape Library Maintenance Information...
Page 526: ...X 6 TS3310 Tape Library Maintenance Information...
Page 529: ......
Page 530: ...Part Number 46X4072 Printed in USA GA32 0478 08 1P P N 46X4072...