Detection Scenario
During the Installation & Verification Test run, any library error occurs that
is not already handled by an existing RAS ticket.
Root Causes
Any function that is executed by the Installation & Verification Test that does
not complete successfully.
Resolution
Perform “DR021: Contact IBM Service” on page 6-68.
T096: Module Communication Error
Description
GUI Description: An error occurred while trying to communicate with a
module.
Explanation: The system is having a problem finding and/or communicating
with all the modules in the library.
Detection Scenario
At boot up, the library cannot determine the status of all modules.
Root Causes
v
Bent pin on a terminator or a module-to-module cable.
v
I/O station sensor error.
v
I2C bus error.
Possible CRU Replacements
v
LCB
v
Module-to-module cable
v
CAN Bus terminator
Possible FRU Replacement
v
CM or EM module
v
I/O Station assembly
v
I/O Lock assembly
Resolution
Perform “DR056: Resolve Module Communication” on page 6-80.
T108: Incompatible Drive Brand
Description
GUI Description: An incompatible drive sled installation has been detected.
Explanation: Different library configurations support different drives. The
drive sleds will contain certain configuration information that the library will
use to validate that the drive is indeed configured properly. If a drive's
configuration data does not match what the library expects, the drive will
not be usable and this ticket will be generated.
Detection Scenario
When drive is installed, the configuration data does not match what is
expected.
Root Causes
v
User installed a drive from a different brand library.
v
User did not purchase the drive from an official TS3310 sales channel.
v
Drive sled does not have the correct configuration information
programmed.
Possible FRU Replacement
Drive sled
Resolution
Perform “DR068: Resolve Incompatible Tape Drive” on page 6-81.
Chapter 6. Service Action Tickets (Txxx) and Diagnostic Resolutions (DRxxx)
6-45
Summary of Contents for System Storage TS3310
Page 2: ......
Page 6: ...iv TS3310 Tape Library Maintenance Information...
Page 8: ...vi TS3310 Tape Library Maintenance Information...
Page 18: ...xvi TS3310 Tape Library Maintenance Information...
Page 20: ...xviii TS3310 Tape Library Maintenance Information...
Page 22: ...xx TS3310 Tape Library Maintenance Information...
Page 28: ...1 6 TS3310 Tape Library Maintenance Information...
Page 76: ...3 14 TS3310 Tape Library Maintenance Information...
Page 92: ...4 16 TS3310 Tape Library Maintenance Information...
Page 196: ...6 94 TS3310 Tape Library Maintenance Information...
Page 242: ...7 46 TS3310 Tape Library Maintenance Information...
Page 378: ...8 136 TS3310 Tape Library Maintenance Information...
Page 382: ...9 4 TS3310 Tape Library Maintenance Information...
Page 390: ...10 8 TS3310 Tape Library Maintenance Information...
Page 396: ...A 6 TS3310 Tape Library Maintenance Information...
Page 415: ...Library Electrical Block a66mi038 Appendix C Library Diagrams C 7...
Page 416: ...Library Control Blade a66mi042 C 8 TS3310 Tape Library Maintenance Information...
Page 417: ...Library Control Blade Functions a66mi039 Appendix C Library Diagrams C 9...
Page 418: ...Accessor Control Block a66mi040 C 10 TS3310 Tape Library Maintenance Information...
Page 421: ...a66mi036 Appendix C Library Diagrams C 13...
Page 423: ...Library Power System a66mi044 Appendix C Library Diagrams C 15...
Page 424: ...a66mi043 C 16 TS3310 Tape Library Maintenance Information...
Page 484: ...D 60 TS3310 Tape Library Maintenance Information...
Page 494: ...E 10 TS3310 Tape Library Maintenance Information...
Page 498: ...F 4 TS3310 Tape Library Maintenance Information...
Page 504: ...G 6 TS3310 Tape Library Maintenance Information...
Page 520: ...H 16 TS3310 Tape Library Maintenance Information...
Page 526: ...X 6 TS3310 Tape Library Maintenance Information...
Page 529: ......
Page 530: ...Part Number 46X4072 Printed in USA GA32 0478 08 1P P N 46X4072...