9.
Troubleshooting
Fieldbus Communication
235
RCP6S
9.4 Driver Alarm
9.4.1 Alarm Level
The alarms are classified to 3 types of levels by the content of the error.
Alarm level
Actuator
status display
LED
*ALM signal
Status when an
error occurred
Content of alarm
Message Green Light is
turned ON.
No output
No stop
Alarm of maintenance output such as
battery voltage drop or the teaching tool
such as PC software
[Refer to Instruction Manual of each tool
for details.]
Operation
release
Red Light is
turned ON.
Output
Servo OFF after
deceleration to
stop
Reset the alarm by the reset signal (RES)
or teaching tool.
Cold start
Red Light is
turned ON.
Output
Servo OFF after
deceleration to
stop
Software reset or power reconnection by
teaching tool.
Home return is required for any actuators
of incremental specification.
Caution: Reset each alarm after identifying and removing the cause.
If the cause of the alarm cannot be removed or when the alarm cannot be reset
after removing the cause, please contact IAI.
If the same error occurs again after resetting the alarm, it means that the cause
of the alarm has not been removed.
9.4.2 Simple Alarm Code
Simple alarm codes are read into the complete position register (PM8 to PM1) of each mode in
Simplified Direct Value, Positioner 1, Positioner 2, Positioner 3 and Positioner 5 when an alarm
is generated.
{
: ON
z
: OFF
*ALM ALM8
(PM8)
ALM4
(PM4)
ALM2
(PM2)
ALM1
(PM1) Binary Code
Description: Alarm code is shown in ( ).
{
z
z
z
z
– Normal
z
z
z
z
{
1
Collision Detection (0DF)
z
z
z
{
z
2
Software reset during servo ON (090)
Position number error during teaching (091)
PWRT signal detected during movement (092)
PWRT signal detected before completion of home
return (093)
z
z
z
{
{
3
Move command during servo OFF (080)
Position command in incomplete home return (082)
Absolute position move command when home
return is not yet completed (083)
Movement command during home return operation
(084)
Position No. error during movement (085)
Position command information data error (0A3)
Command deceleration error (0A7)
z
z
{
z
z
4
Mismatched PCB (0F4)
(Note) *ALM Signal is an active low signal. It is ON when the power is applied to the controller, and
turns OFF when the signal is output.
ME0349-4B
Summary of Contents for RCM-P6AC
Page 2: ......
Page 9: ...Fieldbus Communication RCP6S ME0349 4B ...
Page 32: ...Fieldbus Communication 20 RCP6S ME0349 4B ...
Page 86: ...2 Wiring Fieldbus Communication 74 RCP6S ME0349 4B ...
Page 178: ...3 Operation Fieldbus Communication 166 RCP6S ME0349 4B ...
Page 184: ...4 Vibration Suppress Control Function Fieldbus Communication 172 RCP6S ME0349 4B ...
Page 192: ...6 Power saving Function Fieldbus Communication 180 RCP6S ME0349 4B ...
Page 196: ...7 Absolute Reset Fieldbus Communication 184 RCP6S ME0349 4B ...
Page 284: ......
Page 285: ......