6. Power-saving Function
Fieldbus Communication
178
RCP6S
6.2 Selecting Automatic Current Reduction Feature
When performing a complete stop in the positioning, the current flows in constant amount
(Note 1)
regardless of the size of the external force in a normal condition (without using the automatic
current reduction feature). Using the automatic current reduction feature enables to flow the
current considering the influence of the external force, that will be able to save the power
consumption when the transported load is small.
Note 1 Parameter No. 12 “Current Limit Value at Positioning Stop”
To enabled / disabled the automatic current reduction feature can be set in Parameter No. 182.
Parameter
No.
Name
Unit
Input range
Initial
value
182
Auto Current Adj. Select
-
0: Disabled
1: Enabled
0
Shown below is a graph (example) of the current flow volume and velocity command in the
positioning operation in comparison of when the automatic current reduction feature is inactive
and when it is active.
•
The automatic current reduction feature: Disabled
•
The automatic current reduction feature: Enabled
Time
Current/
Ve
locity
Current Flow Volume
Velocity Command
Current Limit Value at
Positioning Stop
Time
Current/
Ve
locity
Current Flow Volume
Velocity Command
Current flow volume at stop considering external
force influence
Feature dedicated for RCP6S and RCM-P6PC
ME0349-4B
Summary of Contents for RCM-P6AC
Page 2: ......
Page 9: ...Fieldbus Communication RCP6S ME0349 4B ...
Page 32: ...Fieldbus Communication 20 RCP6S ME0349 4B ...
Page 86: ...2 Wiring Fieldbus Communication 74 RCP6S ME0349 4B ...
Page 178: ...3 Operation Fieldbus Communication 166 RCP6S ME0349 4B ...
Page 184: ...4 Vibration Suppress Control Function Fieldbus Communication 172 RCP6S ME0349 4B ...
Page 192: ...6 Power saving Function Fieldbus Communication 180 RCP6S ME0349 4B ...
Page 196: ...7 Absolute Reset Fieldbus Communication 184 RCP6S ME0349 4B ...
Page 284: ......
Page 285: ......