8. Parameter
Fieldbus Communication
221
RCP6S
[70] Selection of SIO2 Baud Rate (Parameter No.169)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
169 Selection of baud rate SIO2
BRSL
bps
9600 to 230400
38400
Set the baud rate in the startup SIO2 baud rate.
Set an appropriate value in accordance with the communication speed of the host.
One of 9600, 14400, 19200, 28800, 38400, 76800, 115200 and 230400 bps can be selected as
the communication speed.
Caution: The baud rate after the PC software is connected will be the rate of PC
software. To make effective the value set in the parameter, turn off the power
once and on it again.
[71] SIO2 Minimum Delay Time for Slave Transmitter Activation (Parameter No.170)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
170 Minimum delay time for slave
transmitter activation
RTM2
msec
0 to 255
5
In this setting, set the time from receiving the command (received data) during the SIO2
communication till the response (sent data) is returned to the host side.
[72] SIO2 Silent Interval Magnification (Parameter No.171)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
171 SIO2 silent interval
magnification
SIM2
Time
0 to 10
0
Use this parameter to set the silent interval (no communication) time by the time taken for
communication of 3.5 characters or longer before command data transmission when the
controller is operated via serial communication.
This parameter need not be changed when a teaching tool such as PC software is used.
If “0” is set, no multiplier is applied.
[73] SIO2 Slave Address (Parameter No.172)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
172 SIO2 slave address
MSA2
-
0 to 16
0
Set the slave addres when SIO2 communication.
(Note) Make sure to establish the setting to avoid duplication of the unit number to a device
connected to SIO2.
Caution: Not to be used in this setting for RCP6S. Do not change the setting from the
setting value.
ME0349-4B
Summary of Contents for RCM-P6AC
Page 2: ......
Page 9: ...Fieldbus Communication RCP6S ME0349 4B ...
Page 32: ...Fieldbus Communication 20 RCP6S ME0349 4B ...
Page 86: ...2 Wiring Fieldbus Communication 74 RCP6S ME0349 4B ...
Page 178: ...3 Operation Fieldbus Communication 166 RCP6S ME0349 4B ...
Page 184: ...4 Vibration Suppress Control Function Fieldbus Communication 172 RCP6S ME0349 4B ...
Page 192: ...6 Power saving Function Fieldbus Communication 180 RCP6S ME0349 4B ...
Page 196: ...7 Absolute Reset Fieldbus Communication 184 RCP6S ME0349 4B ...
Page 284: ......
Page 285: ......