8. Parameter
Fieldbus Communication
210
RCP6S
[45] Absolute unit (Parameter No.83)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
83 Absolute Unit
ETYP
-
0: Not used
1: Used
In accordance
with specification
at order accepted
[For RCP6S and RCM-P6PC]
Set to 1 if simple absolute type or battery-less absolute type and 0 if others.
Set to 0 when using the battery-less absolute in incremental.
[For RCM-P6AC]
Set to 1 for Simple Absolute, and set to 0 for other types.
The battery-less absolute cannot be used in incremental.
[46] Software limit margin (Parameter No.88)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
88 Software Limit Margin
SLMA
mm
(deg)
0 to 9999.99
0
This is the parameter to set the position of over error detection against the soft limit errors set in
Parameters No.3 and No.4.
It is not necessary to change the setting in normal use.
[47] Current limit value at stopping due to miss-pressing (Parameter No.91)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
91 Current Limit Value at Stopping
Due to Miss-pressing
PSFT
-
0: Current limiting
value at stop
1: Current limit value
during pressing
0
This parameter select the restricted current value at stopping due to miss-pressing.
This restricted current value locks the servo till the next moving command.
Set Value
Description
0
Use the current limit value (Parameter No. 12) at positioning
stop.
1
Use the current limit value at pressing set in the position
table.
For RCP6S, RCM-P6PC
and RCM-P6AC only
Error
detection area
Software
limit margin
Soft limit (Parameter No.3, No.4) setting area
Software
limit margin
Error
detection area
ME0349-4B
Summary of Contents for RCM-P6AC
Page 2: ......
Page 9: ...Fieldbus Communication RCP6S ME0349 4B ...
Page 32: ...Fieldbus Communication 20 RCP6S ME0349 4B ...
Page 86: ...2 Wiring Fieldbus Communication 74 RCP6S ME0349 4B ...
Page 178: ...3 Operation Fieldbus Communication 166 RCP6S ME0349 4B ...
Page 184: ...4 Vibration Suppress Control Function Fieldbus Communication 172 RCP6S ME0349 4B ...
Page 192: ...6 Power saving Function Fieldbus Communication 180 RCP6S ME0349 4B ...
Page 196: ...7 Absolute Reset Fieldbus Communication 184 RCP6S ME0349 4B ...
Page 284: ......
Page 285: ......